Unit Installation; Unit Hanging; Ffq-Cxv1 - Daikin FTXN25MV1B Technical Manual

Split unit air conditioner inverter multi split cooling only & heatpump 50hz
Hide thumbs Also See for FTXN25MV1B:
Table of Contents

Advertisement

Unit Installation

• The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).
• Measure and mark the position for the hanging rod. Drill the hole for the angle nut on the ceiling and fi x the
hanging rod.
• The installation template is extended according to temperature and humidity. Check on dimensions in
using.
• The dimensions of the installation template are same as those of the ceiling opening dimensions.
• Before ceiling laminating work is completed, be sure to fi t the installation template to the indoor unit.
Note: Be sure to discuss the ceiling drilling work with the installers concerned.

Unit Hanging

• Confi rm the pitch of the hanging rod is 770mm x 622mm sharp.
• Hold the unit and hand it on the hanging rod with the nut and washer.
• Adjust the unit height to 35.0mm between the indoor unit bottom surface and the ceiling surface.
• Confi rm with a level gauge that the unit is installed horizontally and tighten the nut and bolt to prevent unit
falling and vibration.
• Open the ceiling board along the outer edge of the paper installation template.
15.0
538.0
529.0
32.0
580.0 ~ 610mm (CEILING OPENING MEASUREMENT)

FFQ-CXV1

Indoor Unit
FFQ-CXV1
Application Information
18.0
19.0
Ceiling
Board
30.0mm
11