Error Codes

Error Codes
Error Description
0
Normal
U0
Insuffi cient gas
U2
DC voltage out of range
U4
Communication error
Signal transmission error
U7
(on outdoor unit PCB)
UA
Installation error
Communication Error (indoor and
UF
outdoor) piping and wiring
UH
Anti-freeze function in other room
A1
Indoor PCB error
A3
Water pump error
A5
Antifreeze
A6
Indoor fan motor abnormal
Indoor heat exchanger thermistor short/
C4
open
C9
Indoor room thermistor short/open
Action
No action.
1. Check sensor connection.
2. Check stop valve.
3. Check for gas leak.
4. Check the EXV.
5. Check H8.
1. Check the supply voltage.
2. Check the outdoor fan by rotating with hand.
3. Restart the system.
4. Check power supply waveform.
1. Check the indoor unit - outdoor unit connection wires.
2. Check the voltage of the signal terminal.
3. Check the indoor fan by rotating with hand.
4. Check the power supply waveform.
1. Restart the system.
2. Replace outdoor PCB.
3. Long term monitor on external factor.
1. Check the indoor and outdoor unit model name.
2. Check the part code on the indoor and outdoor PCB.
1. Check the wiring and piping between indoor and outdoor units.
2. Check refrigerant level.
3. Check refrigerant line on blockage.
1. Check which indoor having error A5.
2. Check the supply voltage.
3. Check the indoor and outdoor model name.
1. Check connector connection.
2. Replace indoor PCB.
1. Check for short circuit.
2. Check connection on drain pump.
3. Restart the system.
4. Check the drain water level.
5. Check fl oat switch connection.
1. Check the air passage.
2. Check the intake air fi lter.
3. Check dust accumulation on indoor coil.
4. Check wiring and piping.
5. Check the EXV.
6. Check indoor coil sensor resistance value.
7. Check refrigerant level.
8. Check room sensor resistance value.
1. Check the indoor fan by rotating with hand.
2. Replace indoor fan motor if not rotating smoothly.
3. Check fan motor voltage.
4. Replace indoor PCB if not at the rated voltage.
5. Check fan capacitor's conductivity (AC Motor).
6. Replace fan capacitor if there's conductivity.
1. Check the connector connection.
2. Check the sensor resistance value.
Troubleshooting