Parameter Data Records; Parameter Assignment And Structure Of The Parameter Data Records - Siemens ET 200MP Manual

Automation system
Hide thumbs Also See for ET 200MP:
Table of Contents

Advertisement

Parameter data records

B.1

Parameter assignment and structure of the parameter data records

The data records of the module have an identical structure, regardless of whether you
configure the module with PROFIBUS DP or PROFINET IO.
Dependencies for configuration with GSD file
When a GSD file is used to configure a module, dependencies can arise when "assigning the
parameters".
There are no dependencies for this module. You can assign the individual parameters in any
combination.
Parameter assignment in the user program
You have the option to reconfigure the modules in RUN (e.g. the response of selected
channels to the CPU-STOP state can be changed in RUN without having an effect on the
other channels)
Parameter assignment in RUN
The WRREC instruction is used to transfer the parameters to the module using data records
64 to 79. The parameters set in STEP 7 do not change in the CPU, which means the
parameters set in STEP 7 are still valid after a restart.
The parameters are only checked for plausibility by the module after the transfer.
Output parameter STATUS
The module ignores errors that occurred during the transfer of parameters with the WRREC
instruction and continues operation with the previous parameter assignment. However, a
corresponding error code is written to the STATUS output parameter.
The description of the WRREC instruction and the error codes is available in the STEP 7
online help.
28
Digital output module DQ 16x24...48VUC/125VDC/0.5A ST (6ES7522-5EH00-0AB0)
B
Manual, 11/2015, A5E35683139-AA

Advertisement

Table of Contents
loading

This manual is also suitable for:

S7-1500

Table of Contents