Assignment of data record and channel
For the configuration as a 1 x 16-channel module, the parameters are located in data
records 64 to 79 and are assigned as follows:
● Data record 64 for channel 0
● Data record 65 for channel 1
● ...
● Data record 78 for channel 14
● Data record 79 for channel 15
For the configuration as a 2 x 8-channel module, the module has 2 submodules with eight
channels each. The parameters for the channels are located in data records 64 to 71 and
are assigned as follows:
● Data records 64 to 71 for channels 0 to 7 (submodule 1)
● Data records 64 to 71 for channels 8 to 15 (submodule 2)
Address the respective submodule for data record transfer.
Data record structure
The figure below shows the structure of data record 64 for channel 0 as an example. The
structure is identical for channels 1 to 15. The values in byte 0 and byte 1 are fixed and may
not be changed.
Enable a parameter by setting the corresponding bit to "1".
Figure B-1
Digital output module DQ 16x24...48VUC/125VDC/0.5A ST (6ES7522-5EH00-0AB0)
Manual, 11/2015, A5E35683139-AA
B.1 Parameter assignment and structure of the parameter data records
Structure of data record 64: Bytes 0 to 3
Parameter data records
29