Technical specifications
Output current
for signal "1" rated value
for signal "1" permissible range, max.
Output delay with resistive load
"0" to "1", max.
"1" to "0", max.
Parallel connection of two outputs
For logic operations
For increased performance
For redundant control of a load
Switching frequency
With resistive load, max.
With inductive load, max.
With lamp load, max.
Total current of the outputs
Current per channel, max.
Current per group, max.
Current per module, max.
Cable length
shielded, max.
unshielded, max.
Interrupts/diagnostics/status information
Substitute values can be applied
Interrupts
Diagnostics interrupt
Diagnostics alarms
Diagnostics
Wire break
Short-circuit
Diagnostics indicator LED
RUN LED
ERROR LED
Channel status display
For module diagnostics
Electrical isolation
Electrical isolation of channels
Between the channels
Between the channels, in groups of
Between the channels and backplane bus
Permitted potential difference
Between different circuits
Isolation
Isolation tested with
24
0.5 A
0.6 A
5 ms
5 ms
Yes
No
Yes
25 Hz
0.5 Hz
10 Hz
0.5 A
0.5 A
8 A
1000 m
600 m
Yes
No
No
No
No
Yes; green LED
Yes; red LED
Yes; green LED
Yes; red LED
Yes
1
Yes
125 V DC / 48 V AC
1200 V DC
Digital output module DQ 16x24...48VUC/125VDC/0.5A ST (6ES7522-5EH00-0AB0)
6ES7522-5EH00-0AB0
Manual, 11/2015, A5E35683139-AA