Siemens SITOP PSU8200 24 V/20 A User Manual page 87

3ph
Hide thumbs Also See for SITOP PSU8200 24 V/20 A:
Table of Contents

Advertisement

Table 7- 2
Test voltage for 6EP1437-3BA10
Type test
Production test
Field test
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: < 100 mA
Table 7- 3
Test voltage for 6EP3437-8SB00-0AY0, 6EP3447-8SB00-0AY0 and 6EP3437-8UB00-0AY0
Type test
Production test
Field test
Remark:
Tripping current for DC measurement: 0 mA
Tripping current for AC measurement: < 100 mA
SITOP PSU8200/3800 3ph
Manual, 05.2018, C98130-A7638-A1-6-7629
Test time
Prim ↔ sec (A)
60 s
4200 V DC
60 s
3000 V AC
1 s
2200 V DC
1 s
1500 V AC
1 s
2200 V DC
1 s
1500 V AC
Test time
Prim ↔ sec (A)
60 s
4200 V DC
60 s
3000 V AC
1 s
2540 V DC
1 s
1700 V AC
1 s
2540 V DC
1 s
1700 V AC
Safety, approvals, EMC
Prim ↔ PE (B)
Sec ↔ PE (C)
2200 V DC
700 V DC
1500 V AC
500 V AC
2200 V DC
500 V DC
1500 V AC
350 V AC
2200 V DC
500 V DC
1500 V AC
350 V AC
Prim ↔ PE (B)
Sec ↔ PE (C)
2540 V DC
850 V DC
1700 V AC
600 V AC
2540 V DC
850 V DC
1700 V AC
600 V AC
2540 V DC
850 V DC
1700 V AC
600 V AC
7.2 Test voltage
87

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitop psu8200 36 v/13 aSitop psu8200 48 v/10 aSitop psu8200 48 v/20 aSitop psu3800 24 v/17 aSitop psu3800 12 v/20 aSitop psu3800 24 v/40 a

Table of Contents