Signaling
Red LED lit
Signaling contact,
contact (13, 14) opened
(quiescent position)
LED flashing red
Signaling contact,
contact (13, 14) opened
(quiescent position)
Signaling
Green LED lit
Signaling contact,
contact (13, 14) closed
LED off
Signaling contact,
contact (13, 14) opened
(quiescent position)
Yellow LED lit
Signaling contact,
contact (13, 14) opened
(quiescent position)
Yellow and green LEDs lit
Signaling contact,
contact (13, 14) closed
Red LED lit
Signaling contact,
contact (13, 14) opened
(quiescent position)
LED flashing red
Signaling contact,
contact (13, 14) opened
(quiescent position)
SITOP PSU8200/3800 3ph
Manual, 05.2018, C98130-A7638-A1-6-7629
6EP3446-8SB10-0AY0
(36 V/13 A)
Latching shutdown
-
6EP3424-8UB00-0AY0
(12 V/20 A)
Normal operation, output
voltage > 10 V ± 0.5 V
Supply voltage missing
Overload, output voltage
< 10 V ± 0.5 V (only in the
"constant current" mode)
Phase failure, output voltage
O.K.
Latching shutdown
-
Description, device design, dimension drawing
2.4 Status displays and signaling
6EP3446-8SB00-0AY0
(48 V/10 A)
Latching shutdown
-
6EP3436-8UB00-0AY0
(24 V/17 A)
Normal operation, output
voltage > 20 V ± 0.5 V
Supply voltage missing
Overload, output voltage
< 20 V ± 0.5 V (only in the
"constant current" mode)
Phase failure, output voltage
O.K.
Latching shutdown
-
6EP3447-8SB00-0AY0
(48 V/20 A)
Latching shutdown
Overtemperature → power
OFF/ON after 3 min
6EP3437-8UB00-0AY0
(24 V/40 A)
Normal operation, output
voltage > 20 V ± 1 V
Supply voltage missing
Overload, output voltage
< 20 V ± 1 V
-
Latching shutdown
Overtemperature → power
OFF/ON after 3 min
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitop psu8200 36 v/13 aSitop psu8200 48 v/10 aSitop psu8200 48 v/20 aSitop psu3800 24 v/17 aSitop psu3800 12 v/20 aSitop psu3800 24 v/40 a