Trane TR200 Operator's Manual page 46

Vertical bypass/non bypass panel
Hide thumbs Also See for TR200:
Table of Contents

Advertisement

CAUTION
MOTOR START!
Ensure that motor, system, and any attached equipment is
ready for start. Failure to do so could result in personal
injury or equipment damage.
5.
If a bypass is connected, place the Mode Selector
Switch in drive mode. Apply power by turning
the main disconnect switch to the ON position.
6.
Enter drive programming data per the drive
instruction manual.
7.
Check motor rotation direction in drive control as
follows.
7a
Put panel in drive mode.
7b
Hand start drive at minimum speed (see
drive instruction manual for details).
7c
Confirm directional rotation.
7d
If incorrect, stop the drive, remove
power, and lock out.
7e
Reverse connection of T1 & T2 motor
leads. Do not change incoming power
leads.
7f
Remove lockout and apply power.
7g
Confirm directional rotation.
8.
Check motor rotation direction in bypass as
follows.
8a
Momentarily bump motor in bypass.
8b
Confirm directional rotation.
8c
If incorrect, stop drive, remove power,
and lock out.
8d
Reverse connection of L1 & L2 input
power leads to the main disconnect. Do
not change motor leads.
8e
Confirm directional rotation.
9.
Check motor current in drive mode on the motor
terminals.
9a
Put the unit in drive mode.
9b
Check motor current on motor terminals
T1, T2, and T3. Verify the motor amps
are within drive and motor rated current
and are balanced within 3%. If incorrect,
see 7.1 Start Up Troubleshooting for
isolation procedures.
9c
Check input current on input terminals
L1, L2, and L3. Verify that current is
BAS-SVX49A-EN
within FLA of drive and balanced within
3%. If incorrect, see 7.1 Start Up Trouble-
shooting for isolation procedures.
10.
Check motor current in bypass mode on the
motor terminals.
10a
Put the unit in bypass mode.
10b
Check full load amps on terminals T1,
T2, and T3. Verify the motor amps are
within motor FLA rated current and
balanced within 3%. If incorrect, see
7.1 Start Up Troubleshooting for isolation
procedures.
For steps 11-13, see 5 Electromechanical Bypass (EMB2)
Operation and 6 Electronically Controlled Bypass (ECB)
Operation for details.
11.
Check operation of any optional functions to
confirm that they work, as applicable. Options
may include run permissive, fire mode, common
start/stop, or others.
12.
Exercise the safety circuit and verify that the unit
stops running.
13.
Exercise the start/stop circuit and verify that the
unit starts and stops with the system in the Auto
mode of operation.
Start Up
4-3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents