A 4-position fan speed selector switch located in the control
box allows CFM settings to be field adjustable. Fan speed
control optimizes unit fan speed based on thermostat/room
sensor inputs. The fan speed switch allows for manually setting
an optimal fan speed specific to the application requirements.
Refer to
Table 4
Fan Performance for Constant Torque EC Motor (Sizes 009-012)
Table 20: Constant torque EC motor CFM values
Unit Size
Setting
Function
4 (High)
3 (Standard)
Stage 1
2 (Medium)
1 (Low)
4 (High)
3 (Standard)
Stage 2
2 (Medium)
1 (Low)
009
4 (High)
3 (Standard)
Fan Only
2 (Medium)
1 (Low)
4 (High)
3 (Standard)
Hydronic
Heat
2 (Medium)
1 (Low)
4 (High)
3 (Standard)
Stage 1
2 (Medium)
1 (Low)
4 (High)
3 (Standard)
Stage 2
2 (Medium)
1 (Low)
012
4 (High)
3 (Standard)
Fan Only
2 (Medium)
1 (Low)
4 (High)
3 (Standard)
Hydronic
Heat
2 (Medium)
1 (Low)
Note: 1. EC motor is programmed to make soft starts and stops to reduce stress transmitted to the fan housing. They adjust their speed and torque to deliver constant
airflow over a wide range of external static pressure.
2. Units are shipped at setting 3 (standard). Speed adjustment is done by 4-position switch in the control box.
3. The unit is capable of high-low fan performance through the use of a 2-stage thermostat wired to specific terminals for
High-Low CFM fan performance. Standard operation with a 1-stage thermostat is indicated as stage 2 fan performance.
www.DaikinApplied.com
External Static Pressure (in-H
0 .00
0 .05
0 .10
430
410
390
420
400
380
350
330
310
350
330
310
450
430
410
430
410
390
420
400
380
350
330
310
350
330
310
350
330
310
370
340
310
370
340
310
430
410
390
420
400
380
350
330
310
370
340
310
450
430
410
420
400
380
400
370
350
400
370
350
470
450
430
450
430
410
420
400
380
400
370
350
400
370
350
400
370
350
360
330
300
360
330
300
450
430
410
420
400
380
400
370
350
360
330
300
Figure 55: 4-position fan speed selector switch
O) [Dry Coil and STD Filter) (inches of water column)