(Fc_8); Transfer Switch Failure - Briggs & Stratton 040213 Service And Troubleshooting Manual

15000 watt home generator system
Hide thumbs Also See for 040213:
Table of Contents

Advertisement

(FC_8)

TRANSFER SWITCH FAILURE:

This is an optional feature of the Home Generator
2
System that is designed to display fault conditions that
relate to the transfer switch. It is used with the
and the
EMPOWER™
INTELLIGEN™
systems.
In order for the
"FC_8"
a transfer switch with a compatible control module. Not
all transfer switches will have a control module that will
be compatible.
When
is displayed, it is indicating an open in the
FC_8
transfer switch. An open can occur in:
• The contactor coils
• The limit switches
• The fuse(s)
The
failure code will not be displayed while the
"FC_8"
generator is running (
EXERCISE
Failure). It will not shut down the generator if a
UTILITY
transfer switch failure occurs while the generator is
supplying standby power. The ACCM II monitors the
transfer switch during normal utility power and during
standby power. If a transfer switch failure occurs,
will be displayed at the control panel when power
transfers back to UTILITY.
If a transfer switch failure occurs while the generator is in
mode (not running),
AUTO
control panel.
NOTE
: If so equipped, the CMA simultaneously
signals the remote LED to flash in a sequence of
eight blinks and displays
on the Statstation
Failure"
Page 48
Service & Troubleshooting Guide - Home Generator System - Models 040213 and 040234 (15kW)
series generator
failure code to function, it requires
Mode/
Mode/
MANUAL
will be displayed at the
"FC_8"
"Transfer Switch
display as well.
Fig. 41 Checking Voltage At Fuses In Transfer Switch
"FC_8"
Section 2 - Troubleshooting Information