Combustion
Air and Ventilation
for Appliances
Located
in
Unconfined
Spaces
Unconfined Space is a space whose volume is not less than 50 cubic
feet per 1,000 Btu per hour of the aggregate input rating of all appli-
ances installed in that space. Rooms communicating directly with the
space in which the appliances areinstalled, through openings not fur-
nished with doors, areconsidered a part of the unconfined space.
In unconfined spaces in buildings, infiltration may be adequate to
provide air for combustion, ventilation and dilution of flue gases.
However, in buildings of tight construction (for example, weather
stripping, heavilyinsulated, caulked, vapor barrier, etc.), additionalair
may need to be provided using the methods described in Combustion
Air and Ventilation for Appliances Locatedin Confined Spaces.
Combustion
Air and Ventilation
for Appliances Located in
Confined Spaces
Confined Space is a space whose volume is less than 50 cubic feet per
1,000 Btu per hour of the aggregate input rating of all appliances
installed in that space.
a. ALL AIR FROM INSIDE BUILDINGS:
(See Page 8 Figure 1, and Figure 5 below)
The confined space shall be provided with two permanent open-
ings communicating
directly with an additional room(s) of suffi-
cient volume so that the combined volume of all spaces meets the
criteria for an unconfined space. The total input of all gas utiliza-
tion equipment installed in the combined space shall be considered
in making this determination.
Each opening shall have a minimum
free area of one square inch per 1,000 BTU per hour of the total
input rating of all gas utilization equipment in the confined space,
but not less than 100 square inches. One opening shall commence
within 12 inches of the top and one commencing within 12 inches
of the bottom of the enclosure.
I Figure 5 [
b. ALL AIR FROM OUTDOORS:
(see Figures 6-8)
The confined space shall be provided with two permanent open-
ings, one commencing
within 12 inches of the top and one com-
mencing
within
12 inches from the bottom
orthe
enclosure.
The openings shall communicate
directly, or by ducts, with the
outdoors or spaces (crawl or attic) that freely communicate
with
the outdoors.
Figure 6 1
1. When directly communicating with the outdoors, each opening
shall have a minimum free area of 1 square inch per 4,000 BTU
per hour of total input rating of all equipment in the enclosure.
(See Figure6.)
2. When communicating with the outdoors through vertical ducts,
each opening shall have a minimum free area of I square inch
per 4,000 BTU per hour of total input rating of all equipment in
the enclosure. (See Figure 7.)
I Figure 7 ]
VENTILAT_
LO_I:_
VENT TO
]O_O0_S
Ir_=T AIR DOfff
,,,,,,,,,,,,,,,,A,, , I
3. When communicating with the outdoors through horizontal
ducts, each opening shall have a minimum free area of 1 square
inch per 2,000 BTU per hour of total input rating of all equip-
ment in the enclosure. (See Figure8.)
CEt4T TO
_LrrlxX;_$
Figure 8 1
4. When ducts are used, they shall be of the same cross-sectional area
as the free area of the openings to which they connect. The mini-
mum short side dimension of rectangular air ducts shall nor be
less than 3 inches. (See Figure 8.)
5. Louvers and Grilles: In calculating free area, consideration shall be
given to the blocking effect of louvers, grilles or screens protect-
ing openings. Screens used shall not be smaller than ¼ inch mesh.
If the free area through a design of louver or grille is known, it
should be used in calculating the size opening required to provide
the free area specified. If the design and free area is not known, it
may be assumed that wood louvers will be 20-25 percent free area
and metal louvers and _rilles will have 60-75 percent free area.
Louvers and .grilles shall be fixed in the open position or inter-
locked with the equipment so that they are opened automatically
during equipment operation.
6. Special
Conditions
Created
b7 Mechanical
Exhausting
or
Fireplaces: Operation of exhaust fans, ventilation systems, clothes
dryers or firefplaces may create conditions requiring special atten-
tion to avoica unsarisfactory operation of installed gas utilization
eqmpment.