York Eco 2 Quick Start Up Manual page 31

Packaged rooftop air conditioning units
Table of Contents

Advertisement

TABLE - 6-1 - PARAMETER POINTS LIST (CONT.)
ADDRESS
NUMBER
72/73/74/
ALARM ARRAY
75/76
77
VAV / CV SELECTION
78
HOT GAS REHEAT
79
HOT GAS PRESENT ON COMPRESSOR # 1
80
COMPRESSORS AVAILABLE FOR COOLING
81
STAGES OF HEAT AVAILABLE
82
DUCT STATIC READING
83
BUILDING STATIC PRESSURE
84
LOW AMBIENT KIT INSTALLED
85
BUILDING STATIC PRESSURE SENSOR INSTALLED
86
ERV INSTALLED
87
ERV UNOCCUPIED FAN ENABLE
88
DUCT STATIC SHUTDOWN SETPOINT
JOHNSON CONTROLS
DESCRIPTION
UNITS OF ADJUSTMENT
DATA - 5 CHARACTERS
READ ONLY FLAG
PARAMETER BIT
PARAMETER BIT
PARAMETER BIT
PARAMETER BIT
PRESSURE - INCHES OF
H2O
PRESSURE - INCHES OF
H2O
PARAMETER BIT
PARAMETER BIT
PARAMETER BIT
PARAMETER BIT
PRESSURE - INCHES OF
H2O
FORM 100.50-SU3 (1207)
RANGE OF
CURRENT
ADJUSTMENT
SETTING
0 - 255
0
CV = 0
0
VAV = 1
0 = OFF, 1 = ON
OFF
0 = OFF, 1 = ON
OFF
2 - 4
2
0 - 3
2
0 = DISABLED
0.000 - 5.000
0000
0.000 - 5.000
0000
0 = OFF, 1 = ON
OFF
0 = OFF, 1 = ON
OFF
0 = OFF, 1 = ON
OFF
0 = OFF, 1 = ON
OFF
0.000 - 5.000
4.500
31