TABLE - 6-1 - PARAMETER POINTS LIST (CONT.)
ADDRESS
NUMBER
36
OUTSIDE AIR HUMIDITY SENSOR INSTALLED
37
ECONOMIZER OUTSIDE AIR ENTHALPY SETPOINT
38
RETURN AIR HUMIDITY SENSOR INSTALLED
ECONOMIZER OUTSIDE AIR TEMP ENABLE
39
SETPOINT
40
DEMAND VENTILATION (IAQ) ENABLED
41
IAQ SENSOR RANGE
42
IAQ SETPOINT
43
POWER EXHAUST INSTALLED
44
MODULATING POWER EXHAUST INSTALLED
45
EXHAUST VFD INSTALLED
EXHAUST DAMPER POSITION FOR EXHAUST FAN
46
TO TURN ON (MODULATING ONLY)
EXHAUST DAMPER POSITION FOR EXHAUST FAN
47
TO TURN OFF
ECONOMIZER DAMPER POSITION FOR EXHAUST
48
FAN TO TURN ON (NON-MODULATING ONLY)
ECONOMIZER DAMPER POSITION FOR EXHAUST
49
FAN TO TURN OFF (MODULATING ONLY)
50
APS DATA
51
DIRTY FILTER SWITCH INSTALLED
52
DIRTY FILTER SWITCH DATA
53
COOLING MODE OPERATION ENABLE
54
HEATING MODE ENABLED FOR OPERATION
CONTINUOUS INDOOR FAN OPERATION WITH
55
SENSOR
56
SPACE TEMPERATURE OFFSET RANGE
57
METRIC OPERATION
58
THIRD PARTY BAS ECONOMIZER ENABLED
59
YEAR
60
MONTH
61
DAY OF MONTH
62
DAY OF WEEK
63
HOUR
64
MINUTE
65
SUPPLY AIR TEMP
66
RETURN AIR TEMP
67
OUTSIDE AIR TEMP
68
SPACE TEMP
69
OUTSIDE AIR HUMIDITY
70
RETURN AIR HUMIDITY
71
OCCUPIED INPUT ENABLE
30
DESCRIPTION
UNITS OF ADJUSTMENT
PARAMETER BIT
BTUS PER POUND
PARAMETER BIT
DEGREES F
PARAMETER BIT
PARTS PER MILLION
PARTS PER MILLION
PARAMETER BIT
PARAMETER BIT
PARAMETER BIT
PERCENT OF ECONOMIZER
POSITION
PERCENT OF ECONOMIZER
POSITION
PERCENT OF ECONOMIZER
POSITION
PERCENT OF ECONOMIZER
POSITION
0 = CLOSED,
1 = OPEN
PARAMETER BIT
0 = CLOSED,
1 = OPEN
PARAMETER BIT
PARAMETER BIT
PARAMETER BIT
DEGREES F
PARAMETER BIT
PARAMETER BIT
YEAR (BCD)
MONTH
DAY OF MONTH
DAY OF WEEK
HOURS
MINUTES
DEGREES F
DEGREES F
DEGREES F
DEGREES F
HUMIDITY
HUMIDITY
PARAMETER BIT
FORM 100.50-SU3 (1207)
RANGE OF
CURRENT
ADJUSTMENT
SETTING
0 = OFF, 1 = ON
OFF
10 - 50
27
0 = OFF, 1 = ON
OFF
40º - 80º
55º
0 = OFF, 1 = ON
OFF
0 - 5000 PPM
2000
0 - 5000 PPM
1000
0 = OFF, 1 = ON
ON
0 = OFF, 1 = ON
OFF
0 = OFF, 1 = ON
OFF
0 - 100%
80%
0 - 100%
20%
0 - 100%
60%
0 - 100%
20%
0 = CLOSED,
OPEN
1 = OPEN
0 = OFF, 1 = ON
OFF
0 = OPEN,
OPEN
1 = CLOSED
0 = OFF, 1 = ON
ON
0 = OFF, 1 = ON
ON
0 = OFF, 1 = ON
ON
-5º F - 5º F
0º F
0 = OFF, 1 = ON
OFF
0 = OFF, 1 = ON
OFF
00 - 99
4
1 - 12
1
1 - 31
1
1 - 7
1
0 - 23
0
0 - 59
0
-40º - 180º
0
-40º - 180º
0
-40º - 180º
0
-40º - 180º
0
0% - 100%
0
0% - 100%
0
0 = OFF, 1 = ON
OFF
Continued on next page