HARDWIRED OR COMMUNICATED SPACE SENSOR
CONTROL – HEATING
Field Wiring
Connect the space sensor wiring to the fi eld wiring screw
connections on the Unit Controller (see Appendix 1).
Misc. Connections
Pneumatic tubing must be fi eld-supplied and installed
from the duct static transducer "high" side connection
to a fi eld supplied static pressure probe that is installed
approximately two-thirds down the trunk line in the
duct work. The duct static transducer is mounted in the
control compartment.
An atmospheric static pressure probe with a bracket is
factory supplied (shipped in the return section of the
unit) and is to be installed on the specifi ed support post
(see Appendix 1). A barbed fi tting is already factory
installed on the support post, and should be used to
connect the atmospheric probe using fi eld supplied
pneumatic tubing.
The black cap on the atmospheric
sensor probe should be positioned at
top. See Appendix 1 for details on the
installation of the probe.
Programming
"HEATING MODE OPERATION ENABLED" – Must
be set to ON using Parameter 54 under the PROGRAM
key on the Simplicity control board or under the
HEATING SETUP tab in the Simplicity PC software
package.
"VAV OCCUPIED HEATING ENABLED" – Must be
set to ON using Parameter 26 under the PROGRAM key
on the Simplicity control board or under the HEATING
SETUP tab in the Simplicity PC software package.
JOHNSON CONTROLS
"VAV OCCUPIED HEATING SETPOINT" – Must be
set using Parameter 27 under the PROGRAM key on
the Simplicity control board or under the HEATING
SETUP tab in the Simplicity PC software package.
Settable between 40.0º F and 85.0º F. The default value
is 68.0º F.
"MORNING WARM-UP / VAV RETURN AIR TEMP
SETPOINT" – Must be set using Parameter 29 under
the PROGRAM key on the Simplicity control board or
under the COOLING SETUP tab in the Simplicity PC
software package. Settable between 50.0º F and 85.0º
F. The default value is 70.0º F.
"STAGES OF HEATING AVAILABLE" - Must be set
using Parameter 81 under the PROGRAM key on the
Simplicity control board or under the HEATING SETUP
tab in the Simplicity PC software package.
"DUCT PRESSURE SETPOINT" – Must be set
using Parameter 30 under the PROGRAM key on the
Simplicity control board or under the FAN tab in the
Simplicity PC software package. Settable between 0.0
and 5.0 INWC. The default value is 1.5 INWC.
"DUCT PRESSURE SHUTDOWN SETPOINT" – Must
be set under the FAN tab in the Simplicity PC software
package. Settable between 0.0 and 5.0 INWC. The
default value is 4.5 INWC.
STAND ALONE CONTROL – COOLING
Field Wiring
No additional connections required.
Misc. Connections
Pneumatic tubing must be fi eld-supplied and installed
from the duct static transducer "high" side connection
to a fi eld supplied static pressure probe that is installed
approximately two-thirds down the trunk line in the
duct work. The duct static transducer is mounted in the
control compartment.