Nomenclature; General - York YD480 Series Installation Manual

R-410a 30 - 50 ton 60 hertz
Table of Contents

Advertisement

5012886-YIM-B-0517

Nomenclature

Configured Split Condenser Model Number Nomenclature
Product Category
Y = Split System, Condenser, AC, R-410A
Product Identifier
D = Standard Efficiency, 4-Pipe, R-410A
Nominal Cooling Capacity - MBH
360 = 30 Ton
480 = 40 Ton
600 = 50 Ton
Heat Type & Nominal Heat Capacity
C00 = Cooling Only

General

These condensing units are designed for outdoor installation on
a roof or at ground level. Every unit is completely piped and
wired at the factory and is shipped ready for immediate
installation. Only the liquid and suction lines to the evaporator
coil, the filter drier, the thermostat wiring and the main power
wiring are required to complete the installation. Each unit is
dehydrated, evacuated, leak tested and pressure tested at 450
psig before being pressurized with a holding charge of
refrigerant R-410A for shipment and/or storage.
All controls are located in the front of the unit and are readily
accessible for maintenance, adjustment and service. All wiring
(power and control) can be made through the front of the unit.
2
Y D 360 C00 A 2 A AA 2 A
Product Generation
2 = Second Generation
Installation Options
A = None
B = Option 1
Options
1 = Disconnect
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Airflow
A = Standard Motor
This Split-System (Air Condensing / Air Handling) unit is
one component of an entire system. As such it requires
specific application considerations with regard to the
rest of the system (air handling unit, duct design,
condensing unit, refrigerant piping and control scheme).
Failure to properly apply this equipment with the rest of
the system may result in premature failure and/or
reduced performance / increased costs. Warranty
coverage specifically excludes failures due to improper
application and Unitary Products specifically disclaims
any liability resulting from improper application.
Please refer to the equipment Technical Guide,
Installation Manual and the piping applications bulletin
247077 or call the applications department for Unitary
Products @ 1-877-UPG-SERV for guidance.
Johnson Controls Unitary Products
Product Style
A = Style A
Product Options
AA = None
TA = Technicoat Condenser Coil

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Yd360 seriesYd600 series

Table of Contents