SPLIT-SYSTEM
AIR-COOLED CONDENSING UNITS
YJ-30, -40 & -50
30 THRU 50 NOMINAL TONS

Description

These units are completely assembled, piped and wired at the factory
to provide one-piece shipment and rigging. Each unit is pressurized
with a holding charge of Refrigerant R-410A for storage and/or ship-
ping.
The compact design, clean styling, low silhouette, and quiet operation
make these condensing units suitable for almost any outdoor location.
On rooftops . . . because they weigh much less than a single package
unit of similar capacity and are much easier to rig and support. At
ground level . . . because their ample sub-cooling capacity allows them
to be located three or more stories below the evaporator coil.
Every condenser coil is pressurized with air to 325 psig and leak
tested. After assembly, the unit is pressurized with a combination of
Refrigerant R-410A and nitrogen to 450 psig for pressure testing and
additional leak testing. During this pressure test, the operation of the
high pressure control is checked. As the unit is being evacuated and
dehydrated, the operation of the low pressure control is checked.
Every compressor, condenser fan motor, crankcase heater, and elec-
trical control circuit is checked to assure a trouble-free start-up and
years of reliable operation.
The condenser fan guards are vinyl-coated to provide additional rust
protection and to enhance the appearance of the unit.
Compressors are mounted on rubber isolators to reduce the transmis-
sion of vibration. Vertical discharge condenser fans direct sound
upward and away from any surrounding structures.
All sheet metal parts are constructed of commercial grade galvanized
steel. After fabrication, each part is thoroughly cleaned to remove any
grease or dirt from its surfaces. The external parts are coated with a
powder paint to assure a quality finish for many years. This UL
approved coating system has passed the 750-hour, 20% salt spray
test per ASTM Standard B117.
All models include a 1-year limited warranty on the complete unit. An
additional 4-year extended compressor warranty is available as an
option on all models.
A matching line of Evaporator Blower units is also offered to meet your
precise capacity and air handling requirements.
628792-BTG-G-0418

Advertisement

Table of Contents
loading

Summary of Contents for York YJ-30

  • Page 1: Description

    AIR-COOLED CONDENSING UNITS Every condenser coil is pressurized with air to 325 psig and leak YJ-30, -40 & -50 tested. After assembly, the unit is pressurized with a combination of 30 THRU 50 NOMINAL TONS Refrigerant R-410A and nitrogen to 450 psig for pressure testing and additional leak testing.
  • Page 2: Table Of Contents

    628792-BTG-G-0418 Table of Contents DESCRIPTION ..................1 TABLE OF CONTENTS .
  • Page 3 628792-BTG-G-0418 Product Nomenclature Configured Split Condenser Model Number Nomenclature Y J -30 C00 A T A AA 2 A Product Style A = Style A Product Category Y = Split System, Condenser, AC, R-410A Product Generation 2 = Second Generation Product Identifier Product Options J = Standard Efficiency, 4-Pipe, R-410A...
  • Page 4: Condensing Unit Accessories

    628792-BTG-G-0418 Condensing Unit Features and Benefits • Meets or exceeds ASHRAE 90.1 standards. • Capacity staging for more economical operation and more even temperature levels within the conditioned • Scroll compressors provide both high efficiency and reli- space. ability. ® •...
  • Page 5: Guide Specifications

    • Not exceed those specified on the plans. SPLIT SYSTEM COOLING ONLY CONDENSING UNITS EACH COMPRESSOR SHALL: MODELS YJ-30, -40 AND -50 • Be mounted on isolators to minimize the transmission of vibration. THE INSTALLER SHALL: ALL CONDENSER COILS SHALL: •...
  • Page 6: Physical Data

    628792-BTG-G-0418 Physical Data YJ-30 thru -50 Physical Data Models Component YJ-30 YJ-40 YJ-50 Nominal Tonnage REFRIGERANT Refrigerant type R-410A R-410A R-410A Holding charge (lb) System #1 35.0 47.0 51.0 Operating Charge (lb) System #2 35.0 47.0 51.0 DIMENSIONS (inches) Length 128.5...
  • Page 7: Unit Limitations

    628792-BTG-G-0418 Unit Limitations Condenser Unit limitations Applied Voltage Outdoor DB Temp Cooling (°F) Indoor DB Temp Cooling (°F) Nominal Model Unit Voltage † Tonnage 208/230-3-60 YJ-30 460-3-60 575-3-60 208/230-3-60 YJ-40 460-3-60 575-3-60 208/230-3-60 YJ-50 460-3-60 575-3-60 Rated in accordance with AHRI Standard 110, Range “A” Utilization Voltage.
  • Page 8: Capacity Performance

    628792-BTG-G-0418 Capacity Performance Condenser Only Cooling Capacities YJ-30 thru -50 Condenser Only Capacities Temperature of Air on Condenser Coil, °F Suction Press. & Corresponding MODEL Temp. @ Saturation PSIG °F 275.4 28.5 264.0 27.4 250.0 26.4 238.2 28.8 231.8 32.0 228.5...
  • Page 9: Sound Performance

    Nominal Model dB(A) Tonnage 1000 2000 4000 8000 YJ-30 YJ-40 YJ-50 Rated in accordance with AHRI 270 Standard. Electrical Data YJ-30 thru -50 Electrical Data Compressors Outdoor Fan Motor Minimum Maximum Model Circuit Fuse Size Power Power Ampacity Supply (each)
  • Page 10: Typical Wiring Diagrams

    628792-BTG-G-0418 Typical Wiring Diagrams Typical 208/230 Volt, YJ-30/-40/-50 Condensing Unit Wiring Diagram Ducted Systems...
  • Page 11 628792-BTG-G-0418 Typical Wiring Diagrams Typical 460/575 Volt, YJ-30/-40/-50 Condensing Unit Wiring Diagram Ducted Systems...
  • Page 12 Typical Field Wiring Diagram NJ-30/-40 Evaporator Units, NJ-50 Air Handler and MACZ-50A Evaporator Coil when Matched with YJ-30, -40, -50 Condenser NOTE: Typical field wiring when OD unit is matched with NJ air handler. When matching condensing unit with models other than NJ an additional control transformer is required on the Indoor unit.
  • Page 13 628792-BTG-G-0418 NOTE: For applications on airhandlers/evaporator DX coils line solenoids may be required for proper operation other than NJ-30 thru -50 certified matchups liquid and refrigerant system dump out. Typical NJ-30/-40 & MACZ-50A Liquid Line Solenoid Wiring Ducted Systems...
  • Page 14 628792-BTG-G-0418 Standard Terminal Block on NJ-30/-40 and NJ-50 with MACZ-50A models. On non NJ models isolation relays must be installed to avoid overloading on 75 VA transformer on condensing unit. Primary side of transformer connect to line side of power supply.
  • Page 15: Weight And Dimensions

    Corner Weights & Center Of Gravity (Inches) Unit Dimensions Unit Weight (Lbs.) Weight Weight (Inches) Unit Model Dim X Dim Y A to B D to C Shipping Operation Length Width YJ-30 1875 1895 128.5 88.5 55.2 44.1 YJ-40 2315 2347 128.5 88.5 53.8 44.1...
  • Page 16 628792-BTG-G-0418 REAR LEFT RIGHT FRONT YJ Unit Dimensions Unit Dimensions (Inches) Model YJ-30 128.5 88.5 37.5 41.8 40.0 46.1 37.1 23.6 YJ-40 128.5 88.5 57.7 41.8 40.0 46.1 37.1 23.6 YJ-50 128.5 88.5 57.7 41.8 40.0 46.1 37.1 23.6 Piping And Electrical Connections Piping connections are made from the rear of the unit.
  • Page 17 628792-BTG-G-0418 Piping And Electrical Connection Sizes (30/40/50T) (Inches) Connection Entry Size Suction Line Sys #1 1-5/8 OD Liquid Line Sys #1 7/8 OD Suction Line Sys #2 1-5/8 OD Liquid Line Sys #2 7/8 OD Power Wiring Knockout SEE BELOW Control Wiring 7/8 HOLE Electrical Power Knockout Sizes (Inches)
  • Page 18 628792-BTG-G-0418 Control Wiring Power Wiring 57.689 33.049 29.799 19.358 20.858 22.358 88.140 40 & 50 Ton Power and Control Wiring Connections Ducted Systems...
  • Page 19 SCALE 0.250 88.140 30 Ton Power And Control Wiring Connections Subject to change without notice. Printed in U.S.A. 628792-BTG-G-0418 Copyright © 2018 by Johnson Controls, Inc. All rights reserved. Supersedes: 628792-BTG-F-0218 York International Corporation 5005 York Drive Norman, OK 73069...