Table of contents About this document ................... 5 Applicable documents ..................8 Technical terms and abbreviations ..............8 Revision history ....................9 Safety ....................... 10 Safety instructions ..................10 Safety regulations for the method of operation ..........11 System owner ....................13 Function test / system acceptance / maintenance ........
Page 4
Function test ....................35 13.1 Testing the indicating elements ..............35 System acceptance on site ................ 36 Maintenance ....................37 Glossary ......................40 Index ........................41 4 | 42 Building Technologies A6V10430571_en--_b Fire Safety 2018-07-19...
WARNING The 'Cerberus PACE Cerberus PACE' system is a Class A product which may cause radio ' system is a Class A product which may cause radio interference in a domestic environment in which case the user may be required to...
Page 6
About this document Applicable documents Target groups The information in this document is intended for the following target groups: Target group Activity Qualification System owner ● According to EN 50110-1, ● 'This person can be the owner, 'nominated person with the overall employer, proprietor or a delegated responsibility to ensure the safe person.'...
Page 7
About this document Applicable documents Date format The date format in the document corresponds to the recommendation of international standard ISO 8601 (format YYYY-MM-DD). Conventions for text marking Markups Special markups are shown in this document as follows: ⊳ Requirement for a behavior instruction Behavior instruction with at least two operation sequences –...
About this document Applicable documents 1.1 Applicable documents You will find more information on the Cerberus PACE system and its components in the following documents: Title Document ID IT security policies Cerberus PACE – IT security policies* A6V11439692 System documentation Cerberus PACE –...
About this document Revision history 1.3 Revision history The reference document's version applies to all languages into which the reference document is translated. The first edition of a language version or a country variant may, for example, be version 'd' instead of 'a' if the reference document is already this version. The table below shows this document's revision history: Version Edition date...
Safety Safety instructions 2 Safety Safety 2.1 Safety instructions Safety instructions The safety notices must be observed in order to protect people and The safety notices must be observed in order to protect people and The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: The safety notices in this document contain the following elements: The safety notices in this document contain the following elements:...
National standards, regulations and legislation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant Siemens products are developed and produced in compliance with the relevant Siemens products are developed and produced in compliance with the relevant European and European and international safety standards.
Page 12
Written confirmation must be obtained from malfunctioning and safety risks. Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions. Siemens and the corresponding safety bodies for modifications or additions.
Disregard of the safety regulations Before they are de Before they are delivered, Siemens products are tested to ensure they function livered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries correctly when used properly.
Standards and directives complied with Standards and directives complied with A list of the standards and directives complied A list of the standards and directives complied with is available from your Siemens with is available from your Siemens contact. 2.5.1 Information technology equipment (ITE)
Siemens’ portfolio undergoes continuous development to make it more secure. Siemens strongly recommends that updates are applied as soon as they are available and that the latest versions are used. Use of versions that are no longer supported, and failure to apply the latest updates may increase your exposure to cyber threats.
Operating conditions Operating condition indicators 3 Operating conditions The ↑ voice alarm control and indicating equipment (VACIE) or voice alarm system has the following operating conditions: ● Quiescent condition ● Voice alarm condition ● Fault warning condition ● Disablement condition (option with requirements) 3.1 Operating condition indicators Indicating element colors The light-emitting indicating elements display operating conditions as follows:...
Operating elements in the system The operating elements in a The operating elements in a Cerberus PACE voice alarm system are the call voice alarm system are the call stations and operating terminals with which you can make live announcements and...
Page 18
Call station with electret condenser microphone and gooseneck Call station with electret condenser microphone and gooseneck Call station with electret condenser microphone and gooseneck ● Full network participant in a Full network participant in a Cerberus PACE system system ● 2-line text display line text display ●...
Page 19
Operating elements in the system Operating elements in the system Call stations Desk call station (RS485, 8+1) PT2009 PT2009-A1 ● Call station with 8 configurable, illuminated zone buttons plus speak button configurable, illuminated zone buttons plus speak button ● Electret condenser microphone with gooseneck ●...
Operating elements in the system Operating elements in the system Operating terminals 4.2 Operating terminals Operating terminals System state indicator (door) PT2007-A1 ● EN 54-16-compliant indicator panel for visual and acoustic status for visual and acoustic status messages messages ● Color Color-coded visual indicators: Operation, fault, and alarm coded visual indicators: Operation, fault, and alarm...
Access levels 5 Access levels The access level describes one of several conditions of voice alarm control and indicating equipment (VACIE) in which an appropriately authorized user can have access to or a view of the following functions on the system: ●...
Fire brigade call station (AT) PT2002 Fire brigade call station (AT) PT2002-A1 Operating terminals 6 Fire brigade call station (AT) PT2002 Fire brigade call station (AT) PT2002 Fire brigade call station (AT) PT2002-A1 Microphone with speak button Microphone with speak button Reset button Reset button Speaker...
Fire brigade call station (AT) PT2002-A1 Fire brigade call station operating functions 6.1 Fire brigade call station operating functions Function Design Carrying out manual 1. Lift microphone announcement / triggering evacuation 2. Press and hold speak button 3. Speak into microphone Playing saved voice Press the button labeled accordingly κ...
Page 24
Recurring fault messages ϖ The LED 'FAULT' lights up again. ϖ The fault in the system has not been rectified. 1. Inform Siemens customer support. 2. Request that maintenance be carried out by technical personnel. 24 | 42 Building Technologies...
Desk call station (19 buttons) PT2001 Desk call station (19 buttons) PT2001-A1 Fire brigade call stat Fire brigade call station operation 7 Desk call station (19 buttons) PT2001 Desk call station (19 buttons) PT2001 Desk call station (19 buttons) PT2001-A1 Microphone Microphone LED 'ONLINE' / Fault...
Desk call station (19 buttons) PT2001-A1 Desk call station operating functions 7.1 Desk call station operating functions Function Design Selecting zone Press the button labeled accordingly κ Carrying out manual 1. Press and hold the button labeled as the speak button announcement / triggering evacuation 2.
Page 27
The fault message is reset. Recurring fault messages ϖ The LED 'FAULT' lights up again. ϖ The fault in the system has not been rectified. Inform Siemens customer support. κ Request that maintenance be carried out by technical personnel. 27 | 42...
Key switch for desk call station PTO2002/3 Key switch for desk call station PTO2002/3-A1 Key switch operating functions 8 Key switch for desk call station Key switch for desk call station PTO2002/3 PTO2002/3- Microphone Microphone LED 'ONLINE' / Fault LED 'ONLINE' / Fault Display Display LED 'ON' / Operation...
The buzzer has been silenced. Recurring fault messages ϖ The LED 'FAULT' lights up again. ϖ The fault in the system has not been rectified. Inform Siemens customer support. κ Request that maintenance be carried out by technical personnel. 29 | 42...
The buzzer has been silenced. Recurring fault messages ϖ The LED 'FAULT' lights up again. ϖ The fault in the system has not been rectified. Inform Siemens customer support. κ Request that maintenance be carried out by technical personnel. 30 | 42...
Page 32
Recurring fault messages ϖ The LED 'FAULT' lights up again. ϖ The fault in the system has not been rectified. 1. Inform Siemens customer support. 2. Request that maintenance be carried out by technical personnel. 32 | 42 Building Technologies...
Remote control panel PT2006-A1 Operation PT2006-A1 12.2 Operation PT2006-A1 Switch the output Press the top middle button. κ Output is switched. Switching channel Press the top right button. κ The next channel in ascending order is selected. Press the top left button. κ...
Function test Testing the indicating elements 13 Function test ● The function test must be carried out in accordance with EN 54-16, section 16.2, 'Function tests'. ● Perform the function test on site at the same time as the system acceptance test.
System acceptance on site 14 System acceptance on site The on-site system acceptance test includes all of the function tests in the maintenance table in chapter 'Maintenance [➙ 37]'. 36 | 42 Building Technologies A6V10430571_en--_b Fire Safety 2018-07-19...
Maintenance 15 Maintenance Maintenance The system requires regular maintenance to ensure that it operates reliably. This is The system requires regular maintenance to ensure that it operates reliably. This is The system requires regular maintenance to ensure that it operates reliably. This is all the more true for systems with an evacuation function.
Page 38
Maintenance Cleaning the control panels To clean the control panels, use a wet cloth without any cleaning agents, abrasives, or solvents. See also 1 Function test [➙ 35] 38 | 42 Building Technologies A6V10430571_en--_b Fire Safety 2018-07-19...
Page 39
Maintenance 39 | 42 A6V10430571_en--_b Building Technologies Fire Safety 2018-07-19...
Glossary Glossary Disablement condition Condition in which the disablement of functions is indicated. Fault warning condition Condition in which a fault is indicated. Functional condition Condition of the voice alarm control and indicating equipment, which is identified by its indication on the voice alarm control and indicating equipment.