Siemens Cerberus PACE Operation Manual

Public address and controlled evacuation
Hide thumbs Also See for Cerberus PACE:
Table of Contents

Advertisement

Cerberus PACE
Public Address and Controlled Evacuation
Operation Manual
A6V10430571_en--_c
Smart Infrastructure
2020-06-30

Advertisement

Table of Contents
loading

Summary of Contents for Siemens Cerberus PACE

  • Page 1 Cerberus PACE Public Address and Controlled Evacuation Operation Manual A6V10430571_en--_c Smart Infrastructure 2020-06-30...
  • Page 2 All rights created by patent grant or registration of a utility model or design patent are reserved. Issued by: Siemens Switzerland Ltd. Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724-2424 www.siemens.com/buildingtechnologies Edition: 2020-06-30 Document ID: A6V10430571_en--_c © Siemens Switzerland Ltd, 2018 2 | 57 A6V10430571_en--_c...
  • Page 3: Table Of Contents

    Table of contents About this document ................5 Applicable documents ..................8 Technical terms and abbreviations ..............9 Revision history ....................9 Safety ...................... 10 Safety notes ...................... 10 Safety regulations for the method of operation ........... 11 System owner ....................13 Function test / system acceptance / maintenance ........
  • Page 4 12.1 Operating functions PT2010-A1 ..............41 12.2 Operation PT2010-A1..................42 12.3 Indicator PT2010-A1 ..................43 System status indicator (19") PT2004-A1 ..........44 13.1 Operating functions PT2004-A1 ..............44 13.2 Operation PT2004-A1..................44 13.3 Indicator PT2004-A1 ..................45 System status display (door) PT2007-A1 ..........46 14.1 Operating functions PT2007-A1 ..............
  • Page 5: About This Document

    Support Center, phone +49 89 9221-8000. Goal and purpose This document describes the operation of a ↑ Cerberus PACE voice alarm and announcement system on the ↑ voice alarm control and indicating equipment (VACIE) and the additional operating elements of the voice alarm system.
  • Page 6 About this document Applicable documents Target groups The information in this document is intended for the following target groups: Target group Activity Qualification System owner ● According to EN 50110-1, ● 'This person can be the owner, 'nominated person with the overall employer, proprietor or a responsibility to ensure the safe delegated person.'...
  • Page 7 About this document Applicable documents Conventions for text marking Markups Special markups are shown in this document as follows: Requirement for a behavior instruction Behavior instruction with at least two operation sequences ◈ Behavior instruction with one operation sequence – Version, option, or detailed information for a behavior instruction Intermediate result of a behavior instruction End result of a behavior instruction...
  • Page 8: Applicable Documents

    About this document Applicable documents 1.1 Applicable documents You will find more information on the Cerberus PACE system and its components in the following documents: Title Document ID IT security policies Cerberus PACE – IT security policies A6V11439692 System documentation Cerberus PACE –...
  • Page 9: Technical Terms And Abbreviations

    About this document Technical terms and abbreviations 1.2 Technical terms and abbreviations You will find details of technical terms and abbreviations in the 'Glossary' chapter. 1.3 Revision history The reference document's version applies to all languages into which the reference document is translated. The first edition of a language version or a country variant may, for example, be version 'd' instead of 'a' if the reference document is already this version.
  • Page 10: Safety

    Safety Safety notes 2 Safety 2.1 Safety notes Comply with the following safety notes to protect life, limb, and property. The safety notes in the document include the following elements: ● Symbol for hazard ● Signal word ● Type and source of hazard ●...
  • Page 11: Safety Regulations For The Method Of Operation

    2.2 Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, mounting, installation,...
  • Page 12 Modifications to the system and to individual products may lead to faults, malfunctioning and safety risks. Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions. Modules and spare parts ● Components and spare parts must comply with the technical specifications defined by Siemens.
  • Page 13: System Owner

    System owner Disregard of the safety regulations Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation.
  • Page 14: Standards And Directives Complied With

    ---- End EN 55032 section 4 ---- WARNING The 'Cerberus PACE' system is a Class A product which may cause radio interference in a domestic environment in which case the user may be required to take adequate measures.
  • Page 15: Cyber Security Disclaimer

    Siemens’ portfolio undergoes continuous development to make it more secure. Siemens strongly recommends that updates are applied as soon as they are available and that the latest versions are used. Use of versions that are no longer supported, and failure to apply the latest updates may increase your exposure to cyber threats.
  • Page 16: Operating Conditions

    Operating conditions Operating condition indicators 3 Operating conditions The ↑ voice alarm control and indicating equipment (VACIE) or voice alarm system has the following operating conditions: ● Quiescent condition ● Voice alarm condition ● Fault warning condition 3.1 Operating condition indicators Indicating element colors The light-emitting indicating elements display operating conditions as follows: Color...
  • Page 17: Operating Elements In The System

    Call stations 4 Operating elements in the system The operating elements in a Cerberus PACE voice alarm system are the call stations and operating terminals with which you can make live announcements and play emergency tones and recorded messages in a targeted manner.
  • Page 18 ● Full network participant in a Cerberus PACE system ● 2-line text display ● Buttons and status indicators to control and monitor the Cerberus PACE system by users. The buttons are basically freely operable ● Insertable labels for custom button identification ●...
  • Page 19 Operating elements in the system Call stations PT2009-A1 'Desk call station (RS485, 8+1)' ● Call station with 8 configurable, illuminated zone buttons plus talk button ● Buttons are freely operable ● Electret condenser microphone with gooseneck ● Monitored microphone ● Symmetrical audio transmission, analog ●...
  • Page 20: Operating Terminals

    Operating elements in the system Operating terminals 4.2 Operating terminals PT2010-A1 'System operating unit (19")' ● EN 54-16-compliant indicator panel for visual and acoustic status messages and control voice alarms ● Display of system status ● Control of voice alarms ●...
  • Page 21 Operating elements in the system Operating terminals PT2007-A1 'System state indicator (door)' ● EN 54-16-compliant indicator panel for visual and acoustic status messages ● Color-coded visual indicators: operation, fault, and alarm – Operation: green – Fault: yellow – Voice Alarm: red ●...
  • Page 22: Access Levels

    Access levels 5 Access levels The access level describes one of several conditions of voice alarm control and indicating equipment (VACIE) in which an appropriately authorized user can have access to or a view of the following functions on the system: ●...
  • Page 23: Fire Brigade Call Station (At) Pt2002-A1

    Fire brigade call station (AT) PT2002-A1 Operating terminals 6 Fire brigade call station (AT) PT2002-A1 Microphone with talk button Reset button Speaker LED 'Operation' Configurable announcement LED 'Fault' buttons All-clear button LED 'Engaged' A6V10430571_en--_c 23 | 57...
  • Page 24: Operating Functions Pt2002-A1

    Fire brigade call station (AT) PT2002-A1 Operating functions PT2002-A1 6.1 Operating functions PT2002-A1 Function Design Carrying out manual 1. Lift the microphone announcement / triggering evacuation 2. Press and hold the talk button 3. Talk into the microphone The voice message is audible in all zones ◈...
  • Page 25: Operation Pt2002-A1

    The fault message is reset. Recurring fault messages w The LED 'FAULT' lights up again. w The fault in the system has not been rectified. ◈ Inform Siemens customer support. a Request that maintenance be carried out by technical personnel. A6V10430571_en--_c 25 | 57...
  • Page 26: Fire Brigade Call Station (485, At) Pt2003-A1

    Fire brigade call station (485, AT) PT2003-A1 Operation PT2002-A1 7 Fire brigade call station (485, AT) PT2003-A1 Microphone with talk button Reset button Speaker LED 'Operation' Configurable announcement LED 'Fault' buttons All-clear button LED 'Engaged' 26 | 57 A6V10430571_en--_c...
  • Page 27: Operating Functions Pt2003-A1

    Fire brigade call station (485, AT) PT2003-A1 Operating functions PT2003-A1 7.1 Operating functions PT2003-A1 Function Design Carrying out manual 1. Lift the microphone announcement / triggering evacuation 2. Press and hold the talk button 3. Talk into the microphone The voice message is audible in all zones ◈...
  • Page 28: Operation Pt2003-A1

    The fault message is reset. Recurring fault messages w The LED 'FAULT' lights up again. w The fault in the system has not been rectified. ◈ Inform Siemens customer support. a Request that maintenance be carried out by technical personnel. 28 | 57 A6V10430571_en--_c...
  • Page 29: Desk Call Station (19 Buttons) Pt2001-A1

    Desk call station (19 buttons) PT2001-A1 Operating functions PT2001-A1 8 Desk call station (19 buttons) PT2001-A1 Microphone LED 'ONLINE' / Fault Display LED 'ON' / Operation Speaker (below LED 'ON', not Configurable buttons shown in the graphic) You can create and print the button identification in 'PACE-Design'. 8.1 Operating functions PT2001-A1 Function Design...
  • Page 30: Operation Pt2001-A1

    Desk call station (19 buttons) PT2001-A1 Operation PT2001-A1 8.2 Operation PT2001-A1 Transmitting a manual announcement / Triggering an evacuation with a manual announcement ● Talk button configured as switch 1. Select a zone or several zones by pressing the relevant labeled buttons. a Selected zone buttons light up.
  • Page 31 The fault message is reset. Recurring fault messages w The LED 'FAULT' lights up again. w The fault in the system has not been rectified. ◈ Inform Siemens customer support. a Request that maintenance be carried out by technical personnel. A6V10430571_en--_c 31 | 57...
  • Page 32: Indicator Pt2001-A1

    Desk call station (19 buttons) PT2001-A1 Indicator PT2001-A1 8.3 Indicator PT2001-A1 Color Status Default Description LED ON (5) Green System is in regular operating mode Call station is in alarm mode with activated alarm key or station priority is configured to 8 or higher Call station is not working (no power) LED Online (4) Correct function must be configured with 'PACE-Design':...
  • Page 33: Display Information Pt2001-A1

    Desk call station (19 buttons) PT2001-A1 Display information PT2001-A1 Color Status Default Description PLAY Sound Button (3) is configured as 'PLAY Sound' Green Sound is active Sound is not activated STOP Sound Button (3) is configured as 'STOP Sound' Always Record buffer Button (3) is configured as 'Record buffer' Green...
  • Page 34: Key Switch For Desk Call Station Pto2002/3-A1

    Key switch for desk call station PTO2002/3-A1 Operating functions PTO2002/3-A1 9 Key switch for desk call station PTO2002/3-A1 Microphone LED 'ONLINE' / Fault Display LED 'ON' / Operation Configurable buttons Key switch You can create and print the button identification in 'PACE-Design'. 9.1 Operating functions PTO2002/3-A1 Unlocking/locking the call station Function...
  • Page 35: Desk Call Station (Rs485, 8+1) Pt2009-A1 And Call Station Extension (Rs485, 8) Pto2006-A1

    Desk call station (RS485, 8+1) PT2009-A1 and Call station extension (RS485, 8) PTO2006-A1 Operating functions PT2009-A1 10 Desk call station (RS485, 8+1) PT2009-A1 and Call station extension (RS485, 8) PTO2006-A1 ZONE9 ZONE1 ZONE10 ZONE2 ZONE11 ZONE3 ZONE12 ZONE4 ZONE13 ZONE5 ZONE14 ZONE6 ZONE15...
  • Page 36: Operation Pt2009-A1

    Desk call station (RS485, 8+1) PT2009-A1 and Call station extension (RS485, 8) PTO2006-A1 Operation PT2009-A1 10.2 Operation PT2009-A1 Transmitting a manual announcement / Triggering an evacuation with a manual announcement ● Talk button configured as switch 1. Select a zone or several zones by pressing the relevant labeled buttons. a Selected zone buttons light up.
  • Page 37: Indicator Pt2009-A1

    Desk call station (RS485, 8+1) PT2009-A1 and Call station extension (RS485, 8) PTO2006-A1 Indicator PT2009-A1 10.3 Indicator PT2009-A1 Color Status Default Description Zone Button (3) is configured as 'Zone' Green Zone is selected Zone is activated via the 'Talk' button and the station priority is Green set to 1-7 Zone is activated via the 'Talk' button and the station priority is...
  • Page 38: Desk Call Station (Analog, 3+1) Pt2008-A1

    Desk call station (analog, 3+1) PT2008-A1 Operating functions PT2008-A1 11 Desk call station (analog, 3+1) PT2008- ZONE1 ZONE2 ZONE3 PT2008 Microphone Talk button Configurable buttons You can create and print the button identification in 'PACE-Design'. 11.1 Operating functions PT2008-A1 Function Design ◈...
  • Page 39: Operation Pt2008-A1

    Desk call station (analog, 3+1) PT2008-A1 Operation PT2008-A1 11.2 Operation PT2008-A1 Transmitting a manual announcement ● Talk button configured as switch 1. Select a zone or several zones by pressing the relevant labeled buttons. a Selected zone buttons light up. 2.
  • Page 40: Indicator Pt2008-A1

    Desk call station (analog, 3+1) PT2008-A1 Indicator PT2008-A1 11.3 Indicator PT2008-A1 Color Status Default Description Zone Button (3) is configured as 'Zone' Green Zone is selected Zone is activated via the 'Talk' button and the station priority is Green set to 1-7 Slow Zone is activated via the 'Logic input' and the station priority is blinking...
  • Page 41: System Operating Unit (19") Pt2010-A1

    System operating unit (19") PT2010-A1 Operating functions PT2010-A1 12 System operating unit (19") PT2010-A1 Fault Power Supply Fault FUSE Fault EARTH System ON Fault Voice Alarm Fault NETWORK Fault BUS Fault AMP Fault MIC Silence Buzzer/LED Test Fault Speaker Circuit Start Voice Reset Voice Silence Voice...
  • Page 42: Operation Pt2010-A1

    System operating unit (19") PT2010-A1 Operation PT2010-A1 12.2 Operation PT2010-A1 Silencing an active buzzer w LED 'FAULT' lights up. ◈ Press <Silence Buzzer/LED Test>. a LED 'FAULT' turns off. a The buzzer has been silenced. Performing a test w No buzzer is active. ◈...
  • Page 43: Indicator Pt2010-A1

    System operating unit (19") PT2010-A1 Indicator PT2010-A1 12.3 Indicator PT2010-A1 Color Status Default Description Operating Green System is in regular operating mode System is not working Fault Yellow System has at least one fault No fault in the system Voice Alarm A voice alarm is active in the system System is in quiescent state and no voice alarm is active Start Voice Alarm...
  • Page 44: System Status Indicator (19") Pt2004-A1

    LEDs. Recurring fault messages w The LED 'FAULT' lights up again. w The fault in the system has not been rectified. ◈ Inform Siemens customer support. a Request that maintenance be carried out by technical personnel. 44 | 57 A6V10430571_en--_c...
  • Page 45: Indicator Pt2004-A1

    System status indicator (19") PT2004-A1 Indicator PT2004-A1 13.3 Indicator PT2004-A1 Color Status Default Description Operating Green System is in regular operating mode System is not working Fault Yellow System has at least one fault No fault in the system Voice alarm A voice alarm is active in the system System is in quiescent state and no voice alarm is active A6V10430571_en--_c...
  • Page 46: System Status Display (Door) Pt2007-A1

    LEDs. Recurring fault messages w The LED 'FAULT' lights up again. w The fault in the system has not been rectified. ◈ Inform Siemens customer support. a Request that maintenance be carried out by technical personnel. 46 | 57 A6V10430571_en--_c...
  • Page 47: Indicator Pt2007-A1

    System status display (door) PT2007-A1 Indicator PT2007-A1 14.3 Indicator PT2007-A1 Color Status Default Description Operating Green System is in regular operating mode System is not working Fault Yellow System has at least one fault No fault in the system Voice alarm A voice alarm is active in the system System is in quiescent state and no voice alarm is active A6V10430571_en--_c...
  • Page 48: Alarm Control Panel (19") Pt2005-A1

    Alarm control panel (19") PT2005-A1 Operating functions PT2005-A1 15 Alarm control panel (19") PT2005-A1 <Initiate / Auslösen> indicator <Fault Indication Reset / button Quittieren Störung> button Pre-made cut-out for optional <Reset / Rückstellen> button service socket <Silence / Stumm> indicator button 15.1 Operating functions PT2005-A1 Function...
  • Page 49: Operation Pt2005-A1

    Recurring fault messages w The LED 'FAULT' lights up again. w The fault in the system has not been rectified. ◈ Inform Siemens customer support. a Request that maintenance be carried out by technical personnel. 15.3 Indicator PT2005-A1 Color Status...
  • Page 50: Remote Control Panel Pt2006-A1

    Remote control panel PT2006-A1 Operating functions PT2006-A1 16 Remote control panel PT2006-A1 Player C VOL- MUTE VOL+ <Next channel in descending <Increase sound level> order> <Switch the output> <Mute> <Next channel in ascending <Reduce sound level> order> 16.1 Operating functions PT2006-A1 Function Button Switch the output...
  • Page 51: Operation Pt2006-A1

    Remote control panel PT2006-A1 Operation PT2006-A1 16.2 Operation PT2006-A1 Switch the output ◈ Press the top middle button. a Output is switched. Switching channel ◈ Press the top right button. a The next channel in ascending order is selected. ◈ Press the top left button.
  • Page 52: System Acceptance On Site

    System acceptance on site 17 System acceptance on site The on-site system acceptance test includes all of the function tests in the maintenance table in chapter 'Commissioning and maintenance [➙ 53]'. 52 | 57 A6V10430571_en--_c...
  • Page 53: Commissioning And Maintenance

    Commissioning and maintenance 18 Commissioning and maintenance The system requires commissioning and regular maintenance to ensure that it operates reliably. This is all the more true for systems with an evacuation function. Commission 'maintenance personnel' to perform maintenance work. The following list includes some examples of causes of faults that might be spotted during a function test being performed as part of the maintenance work: ●...
  • Page 54 Commissioning and maintenance Function test ● Carry out the function test at the specified intervals in accordance with the local requirements and standards. ● Perform the function test on site at the same time as the system acceptance test ● If the system is connected to a fire detection installation (FDI), the function test must be performed with the FDI connected.
  • Page 55: Glossary

    Glossary Glossary Fault warning condition Condition in which a fault is indicated. Functional condition Condition of the voice alarm control and indicating equipment, which is identified by its indication on the voice alarm control and indicating equipment. PACE 'Public Address and Controlled Evacuation' Quiescent condition The voice alarm system is supplied with energy and the voice alarm control and indicating equipment exhibits none of the following conditions: voice alarm condition, fault warning condition.
  • Page 56: Index

    Index Index Testing interval ..........54 Access levels ............ 22 Information technology equipment ....14 Access level 1 ............ 22 Access level 2 ............ 22 Maintenance intervals Access level 3 ............ 22 Function test ............53 Access level 4 ............ 22 Original language ..........
  • Page 57 Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd, 2018 Technical specifications and availability subject to change without notice. A6V10430571_en--_c...