Electrical connection

6.6 Conductor connection

6.6
Conductor connection
Cross-sections that can be connected depending on the size of the terminal (possibly
reduced due to size of cable entries)
Table 6- 4
Table 6- 5
80
Max. conductor connection for standard machines and Ex tc
Shaft height
63 ... 90
100 ... 112
132
160 ... 180
200
225
250 ... 280
315
Max. conductor connection for explosion-protected machines (with the exception of Ex
tc) and VIK in the standard version
Shaft height
63 ... 112
132
160
180
180 (1LG4, 1LG6)
200 ... 225
250 ... 280
315
Max. connectable conductor cross-section
mm²
1.5
2.5 with cable lug
4.0
6.0
16.0
25.0
35.0 with cable lug
120.0
240.0
Max. connectable conductor cross-section
mm²
4.0
6.0
16.0
10.0
16.0
50.0
120.0
240.0
1LA5/6/7/9, 1LG4/6, 1MA6/7, 1MB..1/2/3/4/5 - SH 63 ... 355
Operating Instructions, 06/2018, A5E44455710A