Venting Installation - Superior Fireplaces DRL4500 Series Installation And Operation Instructions For

Direct-vent linear gas fireplace
Table of Contents

Advertisement

NOTICE: Read these instructions completely before
attempting installation.
These models are tested and approved for use with an IHP (direct-
vent) pipe components and terminations.
The venting system must terminate on the outside of the structure and
can not be attached to a chimney or flue system serving a separate
solid fuel or gas burning appliance. A direct-vent appliance must
have its own venting system. DO NOT common vent this appliance.
These models are approved to be vented either horizontally through
an outside wall or vertically through a roof or chase enclosure using
the following guidelines:
• When venting system terminates horizontally on an outside wall,
you may install a standoff if the termination cap is to be installed
directly on a combustible finish such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may cause excessive tem-
peratures which could cause a fire.
• Vent pipe air space clearances to combustibles are 1" on all sides
except on the horizontal sections, which requires 2" clearance
from the top of the pipe. Where the termination cap penetrates a
combustible wall, 1" air space clearance is required.
• Have fireplace and selected vent components on hand to help
determine the exact measurements when elbowing or offsetting.
Always use wall firestops when penetrating walls and firestops
when penetrating ceilings or attic spaces.
• For installation of fireplace at elevations of 4000 feet or greater,
pay special attention to venting requirement recommendations.
WARNING: Read all instructions completely and
thoroughly before attempting installation. Failure to
do so could result in serious injury, property damage
or loss of life.
NOTICE: Failure to follow these instructions will void the
warranty.
NOTICE: Do not seal termination cap to vent pipe. Cap
must be removable for vent inspection and mainte-
nance.
INSTALLATION PRECAUTIONS
• Wear gloves and safety glasses for protection
• Use extreme caution when using ladders or when on roof tops
• Be aware of electrical wiring locations in walls and ceilings
The following actions will void the warranty on your venting system:
• Installation of any damaged venting component
• Unauthorized modification of the venting system (Do not cut or alter
vent components)
• Installation of any component part not manufactured or approved
by IHP
• Installation other than as instructed by these instructions
126718-01_G

VENTING INSTALLATION

WARNING: This gas fireplace and vent assembly
must be vented directly to the outside. The venting
system must NEVER be attached to a chimney serving
a separate solid fuel burning appliance. Each direct-
vent gas appliance must use a separate vent system.
Do not use common vent systems.
WARNING: Vent pipe air space clearances to com-
bustibles are 1" on all sides except on the horizontal
sections, which require 2" clearances from the top
of the pipe. Where the termination cap penetrates a
combustible wall, 1" air space clearance is required.
Superiorfireplaces.US.com
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Drl4543tepDrl4543ten

Table of Contents