5.5

VENTILATION AND COOLING

Fig. 5.5-1 Installation on plain floor
The heat produced by the UPS is transferred to the environment by its ventilation.
Air inlets for UPS ventilation are located on the front of the UPS, while air outlets are on top of the
cabinet.
A suitable ventilation or cooling system must be installed to extract the heat from the UPS room.
NOTE !
Do not put anything on the top of the cabinet.
Air filtering systems could be required when the UPS operates in a dirty environment.
In order to prevent overheating of the UPS, the available air intake flow rate must exceed the total air
exhaust flow rate requirement of the UPS system.
Contact your Dealer or the nearest Service Centre for appropriate solutions.
The below table indicates the heat dissipation at full Load at PF = 0.9 & 1 and charged Battery, up to
1000 m (3280 ft) altitude, for cooling air 25°C (77°F) to 30°C (86°F).
UPS model
PF = 0.9
TLE Series 600
20.7 kW
TLE Series 800
27.7 kW
NOTE !
Even when eBoost™ Operating Mode option is available, the ventilation and cooling
system shall be rated as for operation in VFI mode.
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
Losses
VFI
eBoost™ (option)
PF = 1
PF = 0.9
24.3 kW
6.5 kW
32.5 kW
8.7 kW
Fig. 5.5-2 Installation on raised floor
Cooling air flow
PF = 1
PF = 0.9
7.3 kW
6003 m
/h
3
9.7 kW
8033 m
/h
3
User Manual TLE Series 600 & 800 CE S1
VFI
PF = 1
7047 m
/h
3
9425 m
/h
3
Page 35/146