GE TLE series 600 User Manual page 86

600 and 800 kva 400vac ce s1
Table of Contents

Advertisement

Code
4571
OVERLOAD: LOAD ON MAINS
INVERTER AND MAINS
4581
NOT SYNCHRONIZED
4608
ECO CONFIG FAILURE
4697
BATTERY OVERTEMPERATURE
4698
BATTERY POWER INSUFFICIENT
4700
4701
POWER SUPPLY BOARD FAILURE
4702
LOSS OF REDUNDANCY
4900
LOAD LOCKED ON INVERTER
4955
OVERTEMPERATURE
LOAD OFF DUE TO EXTENDED
4998
4999
LOAD OFF DUE TO LOW BATT. OR TEMP.
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
Alarm
DC LOW
OVERLOAD
Description
With Mains Bypass supply available and Load
115%, the Load is transferred on Mains.
Load will be transferred again automatically on
Inverter when Load 100%.
The voltages of Mains and Inverter are not
synchronized, which causes the opening of K6.
The
propagation
of
configuration to other units in a Parallel System
failed.
Detection of Battery overtemperature condition.
Only a GE Service Engineer can reset the alarm.
In case of Mains Failure, with the actual Load, the
run time would be below stop operation time
(default 3 minutes).
Battery voltage is at the lowest limit.
Inverter will remain Off until the battery voltage
reaches the value in parameter.
Detection of a failure on the Power Supply Board,
in particular from the DC supply.
Can be enabled or disabled with respective
parameter.
A time of lost redundancy superior than specified
in respective parameter was detected.
The Load is locked on Inverter after 3 Load
transfers within 30 seconds.
After time out (default 30 sec.) Bypass will be free.
An overtemperature condition has been detected
on Inverter.
Elapsed "stop operation" time, Inverter shut-
down.
With Mains OK, Load is transferred on Mains.
Load Off after time-out of "stop operation" for
overload on Inverter (time depending on the % of
overload).
Load Off after time-out of "stop operation" with
missing Mains due to Battery low voltage or
overtemperature condition.
the
eBoost
/
IEMi
Page 86/146
User Manual TLE Series 600 & 800 CE S1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tle series 800

Table of Contents