Example – Reservoir level monitoring using:
process variable 1 with an engineering range of 0 to 100 feet
logic equation 1 result assigned to relay 1.1 that is used to operate the control valve.
Control
Valve
Alarm B1
Alarm A1
80
50
feet
feet
Flow Conditions
Close reservoir control valve if:
Reservoir level >50 feet AND
rate of change >10 ft/hr
OR
Reservoir level >80 ft
OR
Manual override switch operated
48
Manual Overide
Relay Output
Level Sensor
Input Elements
Alarm A1 set to high process trip at 50 ft
Alarm B1 set to high process trip at 80 ft
Alarm C1 set to fast rate trip at 10% of
range per hour (10 ft/hr)
Manual override switch:
Connected to digital input 1.1
Digital input number
Module number
Negative polarity
Volt-free switching
3 Configuration
Rate of
change
Level
> 10ft/h
Time
Alarm C1
Entering the Logic Equation