3.8 Relay Configuration

Overview.
Relays – can be energized by alarms, logic equation results (math software option enabled by installation of the appropriate
software key), digital inputs, real time events (timer software option enabled by installation of the appropriate software key) and
totalizer wrap signal (totalizer software option enabled by installation of the appropriate software key)
External totalizer count function – external counter can be driven only by Module Type 3 (4-relay module) fitted in module
positions 4, 5 or 6 (see Section 5.2, page 66).
Polarity – allows fail-safe settings
Select Relay Output
Logic Equation 1
Relay 5.1
Relay 5.2
Logic Equation 8
Relay 5.3
Digital Input 1
Relay 5.4
Digital Input 2
Module Position
Relay No.
Alarm A1
Alarm D4
None
42
Relay Source
Source State
Relay Configuration
Press the
key to open the Main Menu.
Highlight Relays.
Select Relay
Select the relay to be configured.
Relay Source
Select the source required to activate the selected relay.
Refer to Appendix A on page 77 for a description of sources.
Relay Polarity
Select the polarity required for the selected relay:
Positive – relay is energized when the relay source is active (On)
Negative – relay is energized when the relay source is inactive (Off)
Return to top of page.
Polarity Selection
Polarity
Alarm A1
Positive
Active
Alarm A1
Negative
Active
Alarm A1
Positive
Inactive
Alarm A1
Negative
Inactive
Relay State
Relay Contacts
NC
Energized
NO
NC
De-energized
NO
NC
De-energized
NO
NC
Energized
NO
3 Configuration