Busbar Installation - Samsung 136S Installation Manual

Lithium ion battery system for ups
Hide thumbs Also See for 136S:
Table of Contents

Advertisement

3.9.3 Busbar Installation

Connect the power busbars between modules
Verify with a voltmeter that no power is present on the
system. Use lock out/tag out procedures to secure the
UPS and batteries.
CAUTION
Please follow the instructions to protect the module BMS against damage.
Important: DO NOT deviate from the sequence of steps below.
The system's voltage will increase proportionally as battery modules are connected.
Exercise extreme caution prevent the terminals from contacting anything except their
intended mounting points.
Terminals and their connected wires have either positive or negative polarity (Positive:
B+, P+; Negative: B-, P-). The polarity of a terminal or a wire connected to the terminal
is on the front of each module and switchgear. Exercise extreme caution to prevent the
terminals and/or wires with opposite polarity from contacting with each other.
It is recommended not to touch the battery positive(+) or negative(-) terminal for the
batteries with rack frame. There is no evidence of dielectric breakdown because of
electrical isolation between the battery positive (+) or negative (-) terminals and rack
frame. However, it is recommended not to touch them for safety because It is possible
to touch between battery positive (+) and negative (-) through the rack frame.
NOTICE
Connect the power busbar with an M8 screw for battery module terminals
When tightening the screws, make sure they are at a straight angle from the
battery module terminals to avoid damage to the nuts inside.
First, assemble the screws using a Phillips-head tip screwdriver using fastening torque
of less than 5.1 Nm (45 in lbs).
Then, use an insulated torque wrench extension with a 13 mm socket. Use fastening
torque of 8.16–11.94 Nm (72–105 in lbs).
NOTICE
Connect the power bus-bar with an M12 screw for switchgear terminals
When tightening the screws, make sure they are at a straight angle from the
switchgear terminals to avoid damage to the nuts inside.
The fastening torque should be 30 Nm (265 in lbs)
Use an insulated torque wrench extension with a 19 mm socket.
Important
The power terminals, such as ―B+,‖ ―B-,‖ ―P+,‖ and ―P-,‖ of the module and Switchgear
are covered with the power terminal cover to guard against a short circuit.
At each step in this process, you must remove the cover prior to connecting a power
busbar and reattach the cover immediately after connecting the power busbars.
ET003222373
English 4/2018. Rev 0.0
.
Assembling the Product
3
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents