F97 Selection Of Copy Function - SMC Networks ZSE20B Operation Manual

Digital pressure switch
Hide thumbs Also See for ZSE20B:
Table of Contents

Advertisement

■[F97] Selection of copy function
The set values of pressure and functions (except for corrected value of fine adjustment of display value and
line name) can be copied. When the pressure range, output and unit specifications are the same, this
function becomes available. The set value can be copied to up to 10 pressure switches simultaneously.
<Connection>
Connect the pressure switches with the power supply turned off.
Connect the FUNC terminals of the master Pressure switch and the slave Pressure switches, and then turn
on the power supply.
The master pressure switch is the switch from which the setting is to be copied.
The slave Pressure switch is the switch to which the setting is to be copied.
When the output specifications of the slave side pressure switch are R, S, T or V, they should be set to
copy input in accordance with the [F 5] FUNC terminal setting (page 39) beforehand.
<Operation>
Press the
or
Selection of copy function
Press the
or
[oFF] (not use) is selected
Press the
Return to function selection
mode.
button of the master Pressure switch in function selection mode to display [F97].
Press the
button.
button to select copy function.
button to set.
Move on to selection of copy function.
[on] (use)
[onL] (use) is selected
Press the
Move to copy ready status.
-56-
button to set.
No.PS※※-OMU0006-A