Table 9: Electrical Data
ZF180-240 - Standard Drive
Size
Volt
(Tons)
RLA
C1
380-3-50
16.7
180
(15)
415-3-50
16.7
380-3-50
18.6
240
(20)
415-3-50
18.6
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
Compressors
OD Fan
(each)
Motors
(each)
LRA
MCC
C2
C1
C2
C1 C2
FLA
13
111 101
26 20.3
2.1
13
111 101
26 20.3
2.1
17.9
118 118
29
28
2.1
17.9
118 118
29
28
2.1
Supply
Pwr
Blower
Conv
Electric Heat Option
Motor
Outlet
FLA
FLA
Model
kW
6.3
0
NONE
6.7
0
NONE
8.2
0
NONE
9.1
0
NONE
5168276-XIM-B-0216
MCA
(Amps)
Stages
Amps
-
-
-
44.4
-
-
-
44.8
-
-
-
53.6
-
-
-
54.5
2
Max Fuse
/
1
3
Breaker
Size
(Amps)
60
60
70
70
17