ABB AC31 Assembly And Operation Manual page 101

Hide thumbs Also See for AC31:
Table of Contents

Advertisement

Table 55: Diagnosis information of the CS31 bus
Channel
Device error:
0
Channel error:
0 ... 7
0 ... 7
Table 56: Device LEDs
LED
PWR
CS31
bus
S-ERR
I/O bus
The S-ERR LED remains on even if the error no longer occurs. The error must be confirmed by
the control system (PLC/central unit), e.g. by means of a function block
data and CS31 bus system data" on page 4.
2018/09/24
The replacement device does not provide a test button to measure functionality.
Error code (COD-
ESYS)
43
45
49
The error codes that are transferred by the replacement device via the CS31
bus bus are newly displayed in CODESYS. Each error code of the CS31 bus
(table column 3) produces the error code in CODESYS (table column 2). As a
result, it is possible to operate the replacement device with a new control
system (PLC/control unit), e.g. 07KT98-ARC-AD, as well as with an old control
system (PLC/central unit), e.g. 07KT98.
An exceedance of the measuring range is signaled even if nothing is connected
to an analog voltage input.
Status
Color LED off
Voltage supply
Gree
n
CS31 bus com-
Gree
munication
n
Error
Red
I/O bus commu-
Gree
nication
n
3ADR010122, 8, en_US
Replacement devices: I/O modules > Replacement device 07AI91-AD
Error code (CS31
bus bus)
1
9
10
LED on
No internal supply
Internal supply
voltage
voltage
No CS31 bus com-
CS31 bus bus
munication
communication
No error
Static error
(must be con-
firmed by the
control system)
No I/O bus commu-
I/O bus com-
nication
munication
AC31 Adapters
Description
Internal error
Cut wire (is also indi-
cated if the current in
measuring range 4 ...
20 mA is less than 2
mA)
Analog value is out of
measuring range
LED flashes
-
Only diagnosis, no
data transfer. Trans-
mission is disturbed.
No CS31 bus con-
nection or activity
Error I/O bus com-
munication
Ä Chapter 1.3 "System
101

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents