TREKKER INSERT
B. Full Reline with Outside Air - Vertical
NOTE: Check clearances carefully for this type of
installation to ensure adequate room for outside
air venting.
Figure 18.1
NOTE: In Canada this fireplace insert must be installed
with a continuous chimney liner extending from
the fireplace insert to the top of the chimney.
The chimney liner must conform to the Class 3
requirements of CAN/ULC-S635, Standard for
Lining Systems for Existing Masonry or Factory-
Built Chimneys and Vents, or CAN/ULC-S640,
Standard for Lining Systems for New Masonry
Chimneys.
18
12 in [305mm]
min. below
Outside Air
Termination at
Chimney Top
(Vertical)
NOTE: In Canada only a full reline is allowed per ULC
S628, ORD ULC C1482-M1990.
12 in [305mm]
min. below
NOTE: Use metal plate around
exhaust vent pipe and seal all edges
with non-flammable insulation such
as fiberglass, mineral wool or
ceramic.
Do not use high temperature
caulking materials to seal any edge
to prevent future serviceability.
Check building codes prior to installation.
Installation MUST comply with local, regional, state
and national codes and regulations.
Consult local building, fire officials or authorities
having jurisdiction about restrictions, installation
inspection, and permits.
7082-153D
CAUTION
September 27, 2018