Remote output function (REM, Pr. 495, Pr. 496)

You can utilize the on/off of the inverter's output signals instead of the remote output terminal of
the programmable logic controller.
Pr.
Name
No.
Remote output
495
selection
Remote output
496
data 1
The above parameters can be set when Pr. 160 = 0.
The above parameters allow its setting to be changed during operation in any operation
mode even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
The output terminal can be turned on/off depending on the Pr. 496 setting. The remote output
selection can be controlled on/off by computer link communication from the PU connector.
Set "96" (positive logic) or "196" (negative logic)" to any of of Pr. 190, Pr. 192 or Pr. 197, and as-
sign the remote output (REM) signal to the terminal used for remote output.
By setting "1", the output terminal turns on (off for sink logic). By setting "0", the output terminal
turns off (on for sink logic) (refer to Fig. 6-57).
Example
When "96" (source logic) is set to Pr. 190 "RUN terminal function selection" and "1" (H01) is
set to Pr. 496, the terminal RUN turns on.
Fig. 6-57: Remote output data
Not assigned (always "0" when read).
FR-D700 SC EC
Initial
Setting
Description
Value
Range
Remote output data
0
clear at powering off
Remote output data
1
retention at powering
off
0
Remote output data
10
clear at powering off
Remote output data
11
retention at powering
off
0
0–4095
Refer to Fig. 6-57
Pr. 496
b
1 1
Function assignment of external terminals
Parameters referred to
190/192/
197
Remote output data
clear at inverter
reset
Remote output data
retention at inverter
reset
Refer to
Section
Output terminal
6.9.5
function selection
b
0
I002083E
6 - 107