Parameter
PID monitor function
The PID control set point, measured value and deviation value can be displayed on the oper-
ation panel and output from terminal AM.
Integral value indicating a negative % can be displayed on the deviation monitor. 0% is dis-
played as 1000. (The deviation monitor cannot be output from the terminal AM.)
For each monitor, set the following value in Pr. 52 "DU/PU main display data selection" and
Pr. 158 "AM terminal function selection".
Setting
52
53
54
Tab. 6-89: PID monitor function
Adjustment procedure
Parameter setting
Terminal setting
FR-D700 SC EC
Monitor Description
PID set point
PID measurement
value
PID deviation value
Adjust the PID control
parameters Pr. 127 to
Pr. 134.
Set the I/O terminals for PID
control. (Pr. 178 to Pr. 182
and Pr. 190, Pr. 192 and
Pr. 197.)
When X14 signal is not
Turn on the
assigned, setting a value
X14 signal
other than "0" in Pr. 128
activates PID operation.
Operation
Minimum
Terminal AM
Increment
Full Scale
0.1%
100%
0.1%
100%
0.1%
Fig. 6-128:
Adjustment procedure
Special operation
Remarks
Value cannot be output from the terminal AM.
The PID deviation value of 0% is displayed
as 1000.
6 - 251