JOGr: During jog reverse rotation
ARAR: At alarm occurrence
n FREQUENCY SETTING
The frequency in PU operation mode and external/PU combined
operation mode (Pr. 79 = "3") can be set. When changing the operation
mode from external operation mode to PU operation mode, operation
mode can not be changed if the external starting signal (STF or STR)
is on.
Direct setting
Directly enter a frequency setting using 0 to 9.
• Operation procedure (Changing from 0Hz setting to 60Hz setting)
1
Press
.
The frequency setting screen
appears.
2
Press
and
.
Enter 60Hz.
*
3
Press
.
The 60Hz setting is complete.
If you entered an incorrect value, press ESC to return to the pre-entry
state.
n SETTING AND CHANGING THE PARAMETER VALUES
Using the FR-PU07/FR-PU07BB allows you to read the parameter of
inverter or change the set value easily. Refer to the inverter instruction
manual for details of the parameters.
Specifying the parameter number to change the set value
Example: When changing 5s to 180s as the Pr. 8 Deceleration time
setting.
1
Press
.
The frequency setting screen
appears to switch to PU
operation mode.
(You need not press
when
the parameter unit is already in
the PU operation mode.)
2
Press
.
The parameter unit enters the
parameter setting mode.
3
Press
.
Enter the desired parameter
number.
4
Press
.
The current setting appears.
5
(1) Direct setting
Press
.
*
Enter the desired value.
Or
Mitsubishi Electric Automation, Inc.
(2) Step setting
Press
.
Freq Set
SET
0.00Hz
0~400Hz
Freq Set
SET
0.00Hz
60.00Hz
0~400Hz
Freq Set
SET
60.00Hz
Completed
Freq Set
SET
0.00Hz
0~400Hz
SETTING MODE
0~9:Ser Pr.NO.
Select Oper
SETTING MODE
Pr.NO.
8
<READ>
8 Dec.T1
5.0S
0~3600
8 Dec.T1
5.0S
180S
0~3600
Enter the desired parameter
number.
4
Press
.
The current setting appears.
5
(1) Direct setting
Press
.
*
Enter the desired value.
Or
(2) Step setting
Press
.
Display "180" using
6
Press
.
The set value is changed.
7
Press
to display the
next parameter.
* If you entered an incorrect value, press to return to the pre-entry
state.

6. OVERVIEW OF FUNCTION MENU

Hold down
to shift one screen.
M
e
n
u
c s
e r
e
n
p
a
g
e
1
M
e
1 MONITOR
5 Alarm Hist
+
2 PU Oper
6 AlarmClear
3 Pr.list
7 INV.Reset
4 Pr.Clear
8 T/Shooting
Press any of the
,
,
and
The functions vary with the inverter model and may be invalid for some
inverters.
Function Menu
Description
The monitor list appears, and you can change from one
1. MONITOR
monitor to another and set the first priority screen.
You can select the PU operation mode via direct input (direct
2. PU Oper
setting with the number keys) or select the jog operation
mode from the PU, and displays how to operate the keys.
The parameter menu appears, and you can perform
3. Pr.List
"parameter setting" , "list display" , "parameter change list
display" and "initial value list display" .
The parameter clear menu appears, and you can perform
4. Pr.Clear
"parameter clear" and "all clear" .
5. Alarm Hist
This function displays history of past eight faults (alarms).
6. AlarmClear
This function clears all the fault (alarm) history.
7. Inv.Reset
This function resets the inverter.
The inverter displays the cause of mismatch between
8. T/Shooting
inverter operation and control/setting or the cause of an
inverter fault.
This function displays the software control number of the
9. S/W
inverter.
This function displays the signals assigned to the I/O
10. Selectop
terminals of the control circuit and the ON-OFF states of the
signals.
This function displays the option fitting states of the option
11. Option
connectors 1 to 3.
The function can perform the "parameter copy" (read, write
12. FRCpy set
verification).
Pr.NO.
8
<READ>
PU07 QUICK START MANUAL
8 Dec.T1
5.0S
0~3600
8 Dec.T1
5.0S
180S
0~3600
.
8 Dec.T1
180.0S
Completed
9 Set THM
2.55A
0~500
and press
n
u
c s
e r
e
n
p
a
g
e
2
M
e
n
u
c s
e r
e
9 S/W
+
10 Selectop
11 Option
12 FRCpy set
keys to switch to the corresponding mode.
n
p
a
g
e
3
5