Download Print this page

Omron E5ED-82 Series Instruction Manual page 2

Digital controller

Advertisement

E5ED-82
Digital Controller
EN
INSTRUCTION MANUAL
Thank you for purchasing the OMRON E5ED Digital Controller.
This manual describes the functions, performance, and
application methods needed for optimum use of the product.
Please observe the following items when using the product.
• This product is designed for use by qualified personnel with
a knowledge of electrical systems.
• Before using the product, thoroughly read and understand
this manual to ensure correct use.
• Keep this manual in a safe location so that it is available for
reference whenever required.
OMRON Corporation
©All Rights Reserved
Refer to the E5D Digital Controllers User's Manual (Cat. No. H224) for detailed
application procedures.
Key to Warning Symbols
Indicates a potentially hazardous situation which, if
not avoided, is likely to result in minor or moderate
injury or property damage. Read this manual
CAUTION
carefully before using the product.
3102754-8B (Side-B)
Wiring
Dimensions
Dimensions (mm)
(64)
Crimp Terminal Sizes: M3
4
60
44
48
1
* You can remove only the interior body of the Digital Controller from the case with the Draw-out Jig to perform maintenance without
removing the terminal leads. Refer to the E5D Digital Controllers User's Manual (Cat. No. H224) for instructions.
* Do not remove the terminal block. Doing so may result in failure or malfunction.
Names of Parts on Front Panel
• °C / °F : temperature unit
The temperature unit is displayed when
the displayed value is a temperature.
Either C or F is displayed according to the
set value of the temperature unit.
• Shift key (PF key)
The default PF Setting parameter is for
shifting the digit. This is a function key.
When it is pressed, the function set for the
PF Setting parameter will operate.
• Level key
Use this key to change levels:
Operation Menu
Input Type
Setting range
Input type
Input
Setting
°C
°F
0
-200 to 850
-300 to 1500
Platinum
1
-199.9 to 500.0
-199.9 to 900.0
Pt100
resistance
2
0.0 to 100.0
0.0 to 210.0
thermometer
3
-199.9 to 500.0
-199.9 to 900.0
JPt100
4
0.0 to 100.0
0.0 to 210.0
5
-200 to 1300
-300 to 2300
Thermocouple
K
6
-20.0 to 500.0
0.0 to 900.0
7
-100 to 850
-100 to 1500
J
8
-20.0 to 400.0
0.0 to 750.0
9
-200 to 400
-300 to 700
T
10
-199.9 to 400.0
-199.9 to 700.0
11
-200 to 600
-300 to 1100
E
12
-100 to 850
-100 to 1500
L
13
-200 to 400
-300 to 700
U
14
-199.9 to 400.0
-199.9 to 700.0
N
15
-200 to 1300
-300 to 2300
16
0 to 1700
0 to 3000
R
S
17
0 to 1700
0 to 3000
B
18
0 to 1800
0 to 3200
19
0 to 2300
0 to 3200
C/W
PL II
20
0 to 1300
0 to 2300
21
0 to 90
0 to 190
10 to 70°C
Infrared
22
0 to 120
0 to 240
60 to 120°C
Thermosensor
23
0 to 165
0 to 320
115 to 165°C
ES1B
140 to 260°C
24
0 to 260
0 to 500
4 to 20mA
25
Current input
Use the following ranges for scaling: -1999
0 to 20mA
26
1 to 5V
27
to 9999, -199.9 to 999.9, -19.99 to 99.99,
Voltage input
0 to 5V
28
-1.999 to 9.999
0 to 10V
29
The default is"5".
s.err will be displayed when a platinum resistance thermometer is mistakenly connected while
input type is not set for it. To clear the s.err display, correct the wiring and cycle the power supply.
Alarms
(Alarms are output from auxiliary outputs.)
Alarm output function
Setting
Alarm type
Positive alarm value (X) Negative alarm value (X)
0
No alarm function
Output off
Vary with
*1
1
Deviation upper/lower limit
"L", "H" values
X
X
ON
2
Deviation upper limit
ON
OFF
OFF
SP
X
ON
ON
3
Deviation lower limit
OFF
OFF
SP
L H
Vary with
ON
Deviation upper/lower range
*1
4
"L", "H" values
OFF
SP
Deviation upper/lower limit
L H
Vary with
ON
*1
5
"L", "H" values
standby sequence ON
OFF
SP
X
X
Deviation upper limit
ON
ON
6
standby sequence ON
OFF
OFF
SP
SP
X
Deviation lower limit
ON
ON
7
standby sequence ON
OFF
OFF
SP
SP
X
Absolute value upper limit
ON
ON
8
OFF
OFF
0
X
Absolute value lower limit
ON
ON
9
OFF
OFF
0
X
Absolute value upper limit
ON
ON
10
OFF
OFF
standby sequence ON
0
X
Absolute value lower limit
ON
11
ON
standby sequence ON
OFF
OFF
0
12
LBA (only for alarm 1)
13
PV Change Rate Alarm
X
ON
ON
14
SP absolute value upper limit
OFF
OFF
0
X
15
SP absolute value lower limit
ON
ON
OFF
OFF
0
X
16
ON
ON
MV absolute value upper limit
OFF
OFF
0
X
ON
ON
17
MV absolute value lower limit
OFF
OFF
0
*1: Upper and lower limits can be set for parameters 1, 4 and 5 to provide for different types
of alarm. These are indicated by the letter "L" and "H".
• The default alarm type is "2"
Warning Symbols
CAUTION
Minor injury due to electric shock may occasionally occur.
Do not touch the terminals while power is being supplied.
Electric shock, fire, or malfunction may occasionally occur. Do not allow metal objects, conductors, debris
(such as cuttings) from installation work, moisture, or other foreign matter to enter the Digital Controller.
Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury
from explosion may occasionally occur.
Never disassemble, modify, or repair the product or touch any of the internal parts. Minor
electric shock, fire, or malfunction may occasionally occur.
CAUTION - Risk of Fire and Electric Shock
a) This is the product UL Listed as Open Type Process Control Equipment. It must be mounted in an enclosure
that does not allow fire to escape externally.
b) More than one disconnect switch may be required to de-energize the equipment before servicing.
c) Signal inputs are SELV, limited energy.
d) Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits.
If the output relays are used past their life expectancy, contact fusing or burning may occasionally
occur. Always consider the application conditions and use the output relays within their rated load
and electrical life expectancy. The life expectancy of output relays varies considerably with the
output load and switching conditions.
The maximum terminal temperature is 75°C. Use wires with a heat resistance of 75°C min to wire the terminals.
Loose screws may occasionally result in fire.
Tighten the terminal screws to the specified torque of 0.43 to 0.58 N•m.
Set the parameters of the product so that they are suitable for the system being controlled. If they
are not suitable, unexpected operation may occasionally result in property damage or accidents.
A malfunction in the Digital Controller may occasionally make control operations impossible
or prevent alarm outputs, resulting in property damage. To maintain safety in the event of
malfunction of the Digital Controller, take appropriate safety measures, such as installing a
monitoring device on a separate line.
Suitability for Use
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which
apply to the combination of the Product in the Buyer's application or use of the Product.
At Buyer's request, Omron will provide applicable third party certification documents identifying ratings and
limitations of use which apply to the Product. This information by itself is not sufficient for a complete
determination of the suitability of the Product in combination with the end product, machine, system, or other
application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer's application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED
FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Installation
Individual mounting (mm )
In the pack:
• Main unit
• Instruction manual
• Watertight packing (Y92S-P9):
• Two adapters (Y92F-51):
Sold Separately
• Terminal cover (E53-COV24)
+ 0.6
45
0
• Draw-out Jig (Y92F-59)
• Front-panel Setup Tool port cover (Y92S-P7)
Operation indicators
• No.1 display
• SUB1: Auxiliary output 1 indicator
Process value or set data type
• SUB2: Auxiliary output 2 indicator
• No.2 display
• OUT1: Control output 1 indicator
Set point, set data read-out value or changed
• OUT2: Control output 2 indicator
input value
• TUNE:
• No. 3 display
Lit during auto-tuning.
(Nothing is displayed at the default settings.)
MV, Soak Time Remain, and Multi-SP.
A:
Flashing or lit during adaptive control.
• Up and Down keys
Each press of U key increments or advances
the values displayed on the No.2 display.
Each press of D key decrements or returns the
values displayed on the No.2 display.
• Mode key
Press this key to change the contents of the display.
Press this button for 1 s or longer for reverse scroll.
• Press the O key and the M key
together for at least 3 seconds to switch to protect level.
Operation stopped.
Initial Setting Level
(Both control and auxiliary outputs are stopped.)
in-t
m-on
2
Model Creation
Input Type *
ON Time
5
0
M
M
Scaling Upper Limit
in-h
m-of
Model Creation
(only when setting
100
analog input)
OFF Time
0
M
M
Scaling Lower Limit
Control Period (Heating)
in-l
cp
(Unit: Seconds)
(only when setting
0
analog input)
*Voltage output
20
(for driving SSR): 2
M
M
Decimal Point
Control Period (Cooling)
dp
c-cp
(only when setting
(Unit: Seconds)
0
analog input)
*Voltage output
20
(for driving SSR): 2
M
M
d-u
c
Direct/Reverse Operation
Temperature
°C=
orev
In Reverse operation
Unit
c
f
°F=
(Heating) =
or-r
In Direct operation
M
(Cooling) =
M
sl-h
SP Upper Limit
alt1
1300
Alarm 1 to 4 Type
M
2
sl-l
M
SP Lower Limit
alh1
-200
Alarm 1 to 4
Hysteresis
M
0.2
PID•ON/OFF
cntl
onof
M
In ON/OFF control =
pid
ev-1
pid
In 2-PID control =
Event Input
M
Assignment 1
msp0
Standard or Heating/Cooling
s-hc
stnd
M
Standard control =
h-c
ev-2
h-c
Heating and cooling control =
Event Input
M
Assignment 2
stop
Adaptive Control
adpt
M
Disabled =
off
Fixed =
fix
p-on
off
Startup Operation
Notification =
info
M
cont
Automatic update =
auto
M
m-pv
Model Creation
bar
Bar Display Data
SP
PV Amplitude
0.0
mv
X
M
M
SP
m-mv
Model Creation
barh
Bar Display Scaling
MV Amplitude
0.0
Upper Limit
100.0
M
barl
Bar Display Scaling
Lower Limit
0.0
M
X
Move to Advanced
amov
Function Setting
0
Level
X
M
0
X
Initial setting level enables users to specify their preferred operating
conditions (input type, alarm type, control method, etc.)
0
X
*2: Refer to the adjoining tables for details of input types and alarm types.
0
*3: Operation is stopped when moved to the initial setting level. (Both control and auxiliary outputs are stopped.)
X
*4: The grayed-out setting items are not displayed for some models and some settings of other setting items.
Typical example: The parameters are not displayed under the following conditions.
0
• AT Execute/Cancel: Not displayed if PID ON/OFF is set to ON/OFF.
• Alarm 1 Type: The default setting is for Controllers that are not equipped with HB/HS alarms.
For a Controller equipped with HB/HS alarms, the Auxiliary Output 1 Assignment parameter (Advanced Function
Setting Level) is set to a heater alarm. If you set alarm 1, the Alarm 1 Type parameter will be displayed.
Refer to the
E
5D Digital Controllers User's Manual (Cat. No. H224) for the setting method.
X
0
X
0
X
0
Conformance to EN/IEC Standards
X
0
This is a class A product.
In residential areas it may cause radio interference, in which case the user
may be required to take adequate measures to reduce interference.
A 급 기기 (업무용 방송통신기자재)
이 기기는 업무용(A 급) 전자파적합기기로서 판매자또는 사용자는 이 점을
주의하시기 바라며, 가정외의지역에서 사용하는 것을 목적으로 합니다.
Conformance to Safety Standard
Due to UL Listing requirements, use the E54-CT1L or E54-CT3L current
transformer with the factory wiring (internal wiring).
Use a UL category XOBA or XOBA7 current transformer that is UL Listed
for field wiring (external wiring) and not the factory wiring (internal wiring).
Always externally connect the recommended fuse that is specified in the
Instruction Manual before you use the Digital Controller.
Analog Input
• If you input an analog voltage or current, set the Input Type parameter to
the correct input type.
• Do not use the Digital Controller to measure a circuit with Measurement
Category II, III, or IV.
• Do not use the Digital Controller to measure an energized circuit to which
a voltage that exceeds 30 Vrms or 60 VDC is applied.
The protection provided by the Digital Controller may be impaired if the Digital
Controller is used in a manner that is not specified by the manufacturer.
Precautions for Safe Use
Be sure to observe the following precautions to prevent operation failure, malfunction, or adverse affects on theperformance
and functions of the product. Not doing so may occasionally result in unexpected events. Use theproduct within specifications.
(1) The product is designed for indoor use only. Do not use the product outdoors. Do not use or store the product in any of
the following locations.
• Places directly subject to heat radiated from heating equipment.
• Places subject to splashing liquid or oil atmosphere.
• Places subject to direct sunlight.
• Places subject to intense temperature change.
• Places subject to icing and condensation.
• Places subject to vibration and large shocks.
• Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas).
(2)
Use and store the Digital Controller within the rated ambient temperature and humidity. Provide forced-cooling if required.
(3)
To allow heat to escape, do not block the area around the product. Do not block the ventilation holes on the product.
(4)
Be sure to wire properly with correct signal name and polarity of terminals.
(5)
Use the specified size of crimped terminals (M3, width 5.8 mm or less) for wiring. To connect bare wires to the terminal
block, use copper braided or solid wires with a gage of AWG24 to AWG18 (equal to a crosssectional area of 0.205 to
2
0.823 mm
). (The stripping length is 6 to 8 mm.). Up to two wires of same size and type, or two crimped terminals can
be inserted into a single terminal.
(6)
Do not wire the terminals which are not used.
(7)
Allow as much space as possible between the controller and devices that generate a powerful high-frequency or surge.
Separate the high-voltage or large-current power lines from other lines, and avoid parallel or common wiring with the
power lines when you are wiring to the terminals.
(8)
Use the Digital Controller within the rated load and power supply.
(9)
Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or relay
contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur.
(10) Make sure that the Digital Controller has 30 minutes or more to warm up after turning ON the power before starting
actual control operations to ensure the correct temperature display.
(11) When using adaptive control, turn ON power for the load at the same time as or before supplying power to the Digital Controller.
(12) During tuning, ensure that the power for the load (e.g., heater) is ON. Otherwise, the correct tuning result cannot be
calculated and optimal control will not be possible. Tuning is used in the following functions:
AT, adaptive control, automatic filter adjustment, and water-cooling output adjustment.
(13) A switch or circuit breaker should be provided close to this unit. The switch or circuit breaker should be within easy
reach of the operator, and must be marked as a disconnecting means for this unit.
(14) Wipe off any dirt from the Digital Controller with a soft dry cloth. Never use thinners, benzine, alcohol, or any cleaners
that contain these or other organic solvents. Deformation or discoloration may occur.
(15) Design system (control panel, etc) considering the 2 second of delay that the controller's output to be set after power ON.
(16) The output will turn OFF when you move to the Initial Setting Level. Take this into consideration when performing control.
(17) The number of non-volatile memory write operations is limited. Therefore, use RAM write mode when frequently
overwriting data during communications or other operations.
(18) When disassembling the Digital Controller for disposal, use suitable tools.
(19) Do not exceed the communications distance that is given in the specifications and use the specified communications cable.
Refer to the E5D Digital Controllers User's Manual (Cat. No. H224) for the communications distance and cable specifications.
(20) Always turn OFF the power supply before pulling out the interior of the product, and never touch nor apply shock to the
terminals or electronic components.
When inserting the interior of the product, do not allow the electronic components to touch the case.
When you insert the interior body into the case, confirm that the hooks on the top and bottom are securely engaged with the case.
If the terminals are corroded, replace the rear case as well.
(21) Do not use the Temperature Controller if the front sheet is peeling.
Side-by-side mounting (mm)
(48 x number of units–2.5) + 1.0
0
Waterproofing is
impossible with
side-by-side installation.
When waterproofing is
required, fit watertight
packing on the
backside of front panel.
• Insert the main unit through the mounting hole in the panel
(1 to 8 mm thickness). Insert the mounting brackets (supplied)
into the fixing slots located on the top and bottom of the rear
case.
• Tighten the two mounting screws on the top and bottom of
the adapter to keep them balanced, and finally tighten them
to a torque of between 0.29 and 0.39 N·m.
• When more than one machine is installed, make sure that the
ambient temperature does not exceed the specified limit.
• STOP: Control stop indicator
Lit when "Run/Stop" is stopped during operation.
During control stop, functions other than control output
are valid.
• CMW: Communications writing enable/ disable indicator
Lit when communications writing is "enabled" and is
out when it is "disabled".
: Protection indicator
Lit when Setting Change Protect is ON (disables the
Up and Down Keys).
• MANU: Manual output indicator
Lit when the Auto/Manual Mode is set to Manual
Mode.
Bar Display: (The default value is heater current.)
Displays the MV or heater current in 10 steps.
*3
Check the wiring before turning ON the power supply.
POWER ON
Operation Level
Process Value/Set Point
25
s.err is displayed when
connected sensor is
0
different from input type.
Hold O down
M
for at least
m-sp
Multi-SP
3 seconds
Set Point Selection
0
(No.1 display flashes,
M
then the control stops.)
sp-m
Set Point During
SP Ramp
Hold O down
0
for at least
M
Heater Current 1
1 second
ct1
or-r
Value Monitor
0.0
(Unit: A)
or-d
M
*2
Leakage Current 1
lcr1
Value Monitor
0.0
(Unit: A)
M
M
Operation level should normally be used during operations.
Hold O and M keys
Hold O and M keys
down for at least 1 second
down for at least 3 seconds
Protect Level
Operation / Adjustment Protect
Restricts displaying and
oapt
modifying menu items in
Operation, Adjustment, and
0
Manual Control Levels.
M
Initial Setting /
Communication Protect
icpt
Restricts movement to the
Initial Setting, Communications
1
Setting, and Advanced Function
M
Setting Levels.
wtpt
Setting Change Protect
Restricts changes to settings
off
by operating the front panel keys.
M
Restricts which settings can be displayed or changed, and restricts
change by key operation.
Press and hold the M Key to cycle through the parameters in reverse.
Error Display (troubleshooting)
When an error has occurred, the No.1 display shows the error code. Take necessary measure
according to the error code, referring the table below.
No.1 display
Meaning
Action
Check the setting of the Input Type parameter,
Input error
s.err
(S. Err)
check the input wiring, and check for broken or
*5
shorts in the temperature sensor.
After the check of input error, turn the power OFF
then back ON again. If the display remains the
A/D converter error
e333
same, the controller must be repaired. If the
(E333)
*5
display is restored to normal, then a probable
cause can be external noise affecting the control
system. Check for external noise.
Turn the power OFF then back ON again. If the
display remains the same, the controller must be
e111
(E111)
Memory error
repaired. If the display is restored to normal, then
a probable cause can be external noise affecting
the control system. Check for external noise.
If the input value exceeds the display limit (-9999 to 9999), though it is within the control
range, [[[[ will be displayed under -1999 and ]]]] above 9999.
Under these conditions, control outputs and alarms will operate normally.
Refer to the E5D Digital Controllers User's Manual (Cat. No. H224) for the controllable ranges.
*5: Error shown only for "Process value / Set point". Not shown for other status.
Connections
(The applicability of the electric terminals varies with the type of machine.)
Control output 1
Control output 2
Auxiliary output 1, 2
Relay output
Relay output
Relay output
250 VAC, 5A (resistive load)
250 VAC, 5A
250 VAC, 3 A
(resistive load)
(resistive load)
Voltage output (for driving SSR)
12 VDC, 40 mA
21 mA if there are
two control outputs
Input Power Supply
Control Outputs 1, 2
A
QR
QQ
100 to 240 VAC
Two voltage outputs
Voltage output
(for driving SSRs)
1
(for driving SSRs)
and relay output
2
3
3
OUT1
OUT1
+
+
Q
Q
-
-
4
4
5
OUT2
5
OUT2
+
Q
R
-
1
6
6
2
3
RR
4
Two relay outputs
5
3
OUT1
6
R
4
7
5
OUT2
8
R
6
9
10
11
12
Auxiliary Outputs
Auxiliary outputs 1 to 2
7
8
9
Auxiliary output 2
10
11
Auxiliary output 1
12
*1. When complying with EMC standards, the line connecting the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
*2. Use non-voltage inputs for the event inputs. The polarity for a non-contact input is indicated by "(-)."
Adjustment Level
AT Execute/Cancel
at
at-2
100%AT Execute
off
at-1
40%AT Execute
M
RUN/STOP
(The No.3 display
cmwt
r-s
Communications Writing
When control start
has been omitted.)
=
run
off
run
When control stop
M
=
stop
Heater Current 1
ct1
M
Value Monitor
al-1
0.0
Alarm Value
Press O
(Unit: A)
1 to 4
M
0
(less than
Heater Burnout
hb1
M
1 second)
Detection 1
al1h
Alarm Value
0.0
(Unit: A)
Upper Limit
M
0
1 to 4
Leakage Current 1
lcr1
M
Value Monitor
al1l
Alarm Value
0.0
(Unit: A)
Lower Limit
0
M
1 to 4
hs1
HS Alarm 1
M
M
(Unit: A)
5 0.0
M
sp-0
SP 0 to 7
0
M
ins
PV
Input Shift
0.0
M
fa
Automatic Filter
Adjustment
off
M
inf
Input Digital Filter
0.0
M
a-ud
PID Update
PF Key Protect
pfpt
(Adaptive Control)
Restricts PF
off
key operation.
off
M
M
w-ht
Water-cooling
Output Adjustment
off
pmsk
Parameter Mask
Enable
M
on
M
Only the value set to the ins: Temperature Input Shift parameter is applied to the entire
temperature input range. When the process value is 200°C, the process value is treated as
201.2°C after input shift if the input shift value is set to 1.2°C. The process value is treated
as 198.8°C after input shift if the input shift value is set to -1.2°C.
Other functions
Refer to the E5D Digital Controllers User's Manual (Cat. No. H224) for information on the
Advanced Function Setting Level, Manual Control Level, and other functions.
Refer to the E5  D Digital Controllers Communications Manual (Cat.No. H225) for information
Status at error
on communications.
Control
Alarm
output
Operates
OFF
as above the
upper limit.
OMRON EUROPE B.V. (Importer in EU)
OFF
OFF
Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands
Phone 31-2356-81-300
FAX 31-2356-81-388
OMRON ELECTRONICS LLC
OFF
OFF
2895 Greenspoint Parkway, Suite 200 Hoffman Estates, IL 60169 U.S.A.
Phone 1-847-843-7900
FAX 1-847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark, Singapore 119967
Phone 65-6835-3011
FAX 65-6835-2711
OMRON Corporation (Manufacturer)
Shiokoji Horikawa, Shimogyo-ku, Kyoto 600-8530 JAPAN
Specifications
Power supply voltage
100 to 240 VAC, 50/60 Hz or
24 VAC, 50/60 Hz / 24VDC
Operating voltage range
85 to 110% of the rated voltage
Power consumption
Option 820:
6.6 VA max. (100 to 240 VAC)
4.1 VA max. (24 VAC)/2.3 W max. (24 VDC)
All other specifications:
8.3 VA max. (100 to 240 VAC)
5.5 VA max. (24 VAC)/3.2 W max. (24 VDC)
Indication accuracy
Thermocouple:
(Ambient temperature: 23°C)
(±0.3 % of indication value or ±1°C,
whichever is greater) ±1 digit max.
Platinum resistance thermometer:
(±0.2 % of indication value or ±0.8°C,
whichever is greater) ±1 digit max.
Analog input: ±0.2 % FS ±1 digit max.
Event input
Output current: approx. 7 mA per contact.
Contact input
ON:1 kΩ max., OFF: 100 kΩ min.
No-contact input
ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
Control output 1
Relay output :SPST-NO
250VAC, 5A (resistive load)
Electrical life of relay: 100,000 operations
Voltage output (for driving SSR):
12 VDC ±20%, 40 mA for one control output,
21 mA if there are two control outputs
Control output 2
Relay output: SPST-NO,
250 VAC, 5 A (resistive load)
Electrical life of relay: 100,000 operations
Control method
ON/OFF or 2-PID control
Auxiliary outputs
Relay outputs: 250 VAC, 3 A (resistive load)
Electrical life of relay: 100,000 operations
Ambient temperature
–10 to 55°C
(Avoid freezing or condensation)
Ambient humidity
25 to 85%
Storage temperature
–25 to 65°C
(Avoid freezing or condensation)
Altitude
Max. 2,000 m
Recommended fuse
T2A, 250 VAC, time-lag, low-breaking capacity
Weight
Approx. 210 g (Digital Controller only)
Degree of protection
Front panel: IP66
Rear case: IP20, Terminal section: IP00
Installation environment
Overvoltage category II, pollution
degree 2 (as per IEC61010-1)
Memory protection
Non-volatile memory
(Number of write operations: 1,000,000)
Do not connect anything to the terminals that are shaded gray.
E5ED-@ @ @ @ DM-82@
Options
Input Power Supply
Auxiliary Outputs
Control Outputs 1, 2
Options
D
820
821
828
24 VAC/DC
Two event inputs,
Communications, two
1
and one CT
event inputs, and one CT
B(+)
2
13
13
13
RS-485
14
14
14
(no polarity)
A(−)
15
15
15
(
)
(
)
16
16
16
17
17
17
13
EV1
EV1
18
18
18
14
EV2
EV2
19
19
19
15
CT1
CT1
20
20
20
16
21
21
21
17
18
19
20
Sensor Temperature/Analog Input
21
TC
Pt
I
V
A
+
22
22
22
22
22
B
mA
23
23
23
23
23
B
V
24
24
24
24
24
+
+
The E5ED is set for a K thermocouple
(input type of 5) by default. If a different
sensor is used, an input error (s.err) will
occur. Check the setting of the Input Type
parameter.
Water-cooling
w-il
d-p
Disturbance
Proportional Band
Proportional Band
1.4
8.0
Increase Threshold
M
M
Water-cooling
Disturbance
d-i
w-dl
Proportional
Integral Time
Band Decrease
(Unit: Seconds)
233
0.6
Threshold
M
M
Disturbance
d-d
p
Proportional
Derivative Time
Band
40
(Unit: Seconds)
8.0
M
M
c-db
i
Integral Time
Dead Band
(Unit: Seconds)
0.0
233
M
M
Manual Reset Value
d
of-r
Derivative Time
Clears the offset
(Unit: Seconds)
40
50.0
during P or PD control.
M
M
c-p
Proportional
hys
Hysteresis
Band (Cooling)
(Heating)
300.0
1.0
M
M
Integral Time
c-i
chys
Hysteresis
(Cooling)
233
(Cooling)
(Unit: Seconds)
1.0
M
M
Derivative Time
c-d
(Cooling)
sprt
40
(Unit: Seconds)
SP Ramp Set Value
off
M
M
sp-p
SP Response
Proportional Band
ol-h
8.0
MV Upper Limit
M
100.0
SP Response
sp-i
M
Integral Time
ol-l
233
(Unit: Seconds)
MV Lower Limit
-100.0
M
SP Response
sp-d
M
Derivative Time
40
plcm
(Unit: Seconds)
Communications
Monitor
M
0
SP Response
sp-n
M
Coefficient
0
Number
M
Adjustment level is for entering set values and
shift values for control.

Advertisement

loading