Potterton Paramount five 50 Installation Manual page 121

Gas condensing boiler
Table of Contents

Advertisement

Tab.23
Check no. heat source 1 (prog.-no. 6212)
Number
K8
(1)
(part 1)
0
1
3
5
X
6
7703046 - 01 - 23072018
Solar
K8
K18
K18
(2)
(3)
No solar
X
Time constant building (6110)
The value set here influences the reaction speed of the flow setpoint in
case of fluctuating outside temperatures as a function of the building
design.
Example values (refer also to Quick setback):
40 for buildings with thick walls or outer insulation.
20 for buildings of normal building design.
10 for buildings of light building design.
For more information, see
Quick setback (780, 1080, 1380), page 91
Optimum start control max (790, 1090, 1390) and Optimum stop
control max (791, 1091, 1391), page 92
Central setp compensation (6117)
The central setpoint lead monitors the heat generator setpoint to the
required central flow temperature. With the setting the maximum corrector
is restricted, even if a larger adaptation should be required.
Frost protection plant (6120)
The heating circuit pump is activated without heat request subject to
outside temperature. If the outside temperature reaches the lower limit
value of -4°C, the heating circuit pump is activated. The pump is activated
every 6 hours for 10 minutes when the outside temperature is between
-5°C and +1.5°C. When the upper limit value of 1.5°C is reached, the
pump switches off.
Water pressure min (6181)
A maintenance message is indicated from this set water pressure. The
boiler output is reduced by 20% to protect the boiler. The message is only
reset when the set pressure has been exceeded by 0.2 bar.
Save sensors (6200)
Sensor modes can be saved under prog. no. 6200. This is done
automatically; however, after change of the heating system (removal of a
sensor) the state must be saved again to the sensor terminals.
Reset to default parameters (6205)
The factory setting of the regulator is written to the regulator.
Caution
The regulator parameters are overwritten. The factory settings are
stored in the regulator.
Activation of prog. no. 6205:
The regulator is reset to factory setting.
Check no. heat source 1 (6212), Check no. heat source 2
(6213), Check no. storage tank (6215) and Check no. heating
circuits (6217)
The standard device generates a check number to identify the system
scheme; this comprises the numbers listed in the table below.
Number
K9
(4)
(5)
(part 2)
(6)
DHW/B
Boiler
Modulating burn­
er
00
No boiler
01
02
03
04
Paramount five 30 – 115
9 Settings
Boiler pump
X
X
121