The setpoint is set under prog.no. 1859/1909.
Release swi pool source heat: activation triggers heating of the
swimming pool by the heat source.
Excess heat discharge: Active excess heat discharge enables, for
example, an external source to force consumers (heating circuit, DHW
storage tank, Hx pump) to draw off excess heat with a signal. For each
consumer the parameter excess temperature discharge can be set to
determine whether the forced signal is taken into account and should
therefore take part in the heat discharge or not.
Release swi pool solar: This function enables the solar swimming pool
heater to be released externally (e.g. via a manual switch) or the solar
charging priority to be specified as compared to the storage.
Operating level DHW: The operating level can be set via the contact
instead of via the internal time program (external time program)
Room thermostat HC1 to Room thermostat HC3: With the input a room
thermostat request can be generated for the set heating circuit.
Important
The quick decrease should be switched off for the corresponding
heating circuits.
DHW thermostat: Connection of the DHW thermostat.
Pulse count: By querying the input the low frequency pulse, e.g. for flow
measurement is recorded.
Checkb sign flue gas damper: Feedback via input H1 in case of
activated flue gas damper control.
Start prevention: With this input a burner start can be prevented. The
boiler also remains blocked for all other protection functions.
Consumer request VK1 10V/Consumer request VK2 10V: The
application node external load x receives a voltage signal (DC 0...10 V)
as heat request. The linear curve is defined via two fix points (voltage
value 1/function value 1 and voltage value 2/function value 2 (only
applies to H1).
Output request 10V: The generator receives a voltage signal (DC 0...10
V) as output request. The linear curve is defined via two fix points
(voltage value 1/function value 1 and voltage value 2 / function value 2
(only applies to H1).
Temp measurement 10V: The controller receives a voltage signal (0 - 10
V DC) as a signal for the measured temperature. The corresponding
temperature is calculated via the linear curve, which is defined via two
fixed points (voltage value 1/function value 1 and voltage value 2/
function value 2).
For more information, see
Optg mode changeover (900, 1200, 1500), page 95
Flow temp setp cons request (1859, 1909, 1959), page 97
Contact type H1 (5951) Contact type H4 (5971) and Contact
type H5 (5978)
With this function, the contacts can be set as resting contact (contact
closed, must be opened for activating the function) or as working contact
(contact opened, must be closed for activating the function).