Wireless Sensor Specifications

Table 23. Wireless sensor specifications
Component
Sensor operating temperature
Receiver operating temperature
Storage temperature
Storage and operating humidity range
Accuracy
Resolution
Setpoint functional range (WDS only)
Receiver voltage
Receiver power consumption
Housing
Mounting
Sensor battery
(a)
Range
Output power
Radio frequency
Radio channels
Address range
Minimum time between transmissions
Maximum time between transmissions
(a) Range values are estimated transmission distances for satisfactory operation. Actual distance is job specific and must be determined during site eval-
uation.

Agency Compliance

Table 24. Agency compliance information for wireless sensors
Agency
United States compliance
(all models)
Canada compliance
(all models)
IEEE compliance for radio
frequency range
(all models)
UNT-SVX07E-EN
Type
32°F to 122°F
-40°F to 158°F
-40°F to 185°F
5% to 95%, non-condensing
0.5°F over a range of 55ºF to 85°F
0.125°F over a range of 60°F to 80°F 0.25°F when outside this range
50°F to 89.6°F
24 V nominal ac/dc ±10%
<1 VA
Polycarbonate/ABS blend, UV protected, UL 94-5VA flammability rating, suitable for application in a
plenum
3.24 in (8.26 cm) for 2 mounting screws (supplied)
(2) AA, 1.5 V, 2800 mAh, lithium, 5-year life, UL listed
Open range: 2,500 ft (762 m) (packet error rate = 2 percent)
Usable: 200 ft (61 m)
Typical: 75 ft (23 m)
100 mW
2.4 GHz (IEEE Std 802.15.4-2003 compliant)
(2405 to 2480 MHz, 5 MHz spacing)
16
000 to 999
30 seconds
15 minutes
Compliance
UL listed: UL 94-5VA Flammability rating
UL 916: Energy management equipment
FCC CFR47, Section 15.247 & Subpart E Digital Modulation Transmission with no SAR (FCC Identification TFP-
13651127)
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1.
This device may not cause harmful interference, and
2.
This device must accept any interference received,
including interference that may cause undesired operation.
Warning: Changes or modifications not expressly approved by the party responsible for compliance could void
the user's authority to operate the equipment.
20 cm separation distance:
To comply with FCC's RF exposure limits for general population/uncontrolled exposure, the antenna(s) used for
this transmitter must be installed to provide a separation distance of at least 20 cm from all persons and must
not be co-located or operating in conjunction with any other antenna or transmitter.
CSA22.2 No. 205-M1983 Signal Equipment
Industry Canada (Certification no: IC: 6178A-13651127)
Industry Canada statement:
the term "IC" before the certification/registration number signifies only that the Industry Canada technical
specifications were met.
Section 14 of RSS-210:
The installer of this radio equipment must ensure that the antenna is located or pointed such that it does not
emit RF field in excess of Health Canada limits for the general population.
IEEE 802.15.4-2003, IEEE Standard for Information Technology—Telecommunications and information
exchange between systems—Local and metropolitan area networks—Specific requirements, Part 15.4: Wireless
Medium Access Control (MAC) and Physical Layer (PHY) Specifications for Low Rate Wireless Personal Area
Networks (LR-WPANs)