Setting standard inputs

Wiring
Wiring example of reset switch, start switch, and stop switch to CC-Link IE Field Network remote I/O module (NZ2GF2B1-
16D)
Terminal block for
power supply and FG
24VDC
Terminal block for input
Reset switch (NO)
Start switch (NO)
Stop switch (NC)
24VDC
Example of parameter setting
Item
Input response time
Output HOLD/CLEAR setting
Cyclic data update watch time setting
Mode switch
Initial operation setting
Synchronous input timing acquisition function
Input off delay setting X0 to XF
CCIEF remote (A-2) (A = 2, 3, 4)
NZ2GF2B1-16D
A1
+24V
A2
24G
A3
FG
1
X0
2
X1
3
X2
16
XF
17
COM
18
COM
Description
10ms
CLEAR
0
Automatical judgment mode
With initial processing
Invalid
0
5 SAFETY APPLICATION CONFIGURATION EXAMPLES
5.2 System to Which Multiple Safety CPUs are Connected