Omron CJ1W-CORT21 Operation Manual page 81

Cj-series. user defined can unit nj-series cpu unit
Hide thumbs Also See for CJ1W-CORT21:
Table of Contents

Advertisement

Name of device variables for
CJ-series Unit
*_NetPwrErr
*_BusoffErr
*_ErrInErrLog
CJ-series User Defined CAN Unit Operation Manual for NJ-series CPU Unit (W517)
3 Data Exchange with the CPU Unit
Type
R/W
Area
BOOL
R
Network-
Power Fail-
ure
BOOL
R
Bus Off
Event
BOOL
R
Error in
Error Log
Function
<Operation specifications>
TRUE:
Error ER10 active indicating a power fail-
ure while communicating.
FALSE:
Network power is within acceptable range.
Default: FALSE
<Operation specifications>
TRUE:
A bus off event EV5 (bus off) has been
generated. Reset to FALSE when
*_EnblCANComm is switched from
FALSE→TRUE in state ST4 (configured).
FALSE:
A bus off event did not occur since the last
EV3 event (enable communications).
Default: FALSE
<Operation specifications>
TRUE:
New errors present in error log since:
• Startup
• Last service of message command
2102
• Last service of message command
2103
FALSE
No new errors in error log since:
• Startup
• Last service of message command
2102
• Last service of message command
2103
Default: FALSE
3
3-11

Advertisement

Table of Contents
loading

Table of Contents