Omron CJ1W-CORT21 Operation Manual page 80

Cj-series. user defined can unit nj-series cpu unit
Hide thumbs Also See for CJ1W-CORT21:
Table of Contents

Advertisement

3 Data Exchange with the CPU Unit
The following device variables for CJ-series Unit are used to reference individual information.
Name of device variables for
CJ-series Unit
*_EnblComm
*_MsgRcv
*_SendOver
*_RcvOver
3-10
Type
R/W
Area
BOOL
R
Enabled
Communi-
cation
BOOL
R
CAN Mes-
sage
Received
BOOL
R
Send
Queue
Overflow
BOOL
R
Receive
Queue
Overflow
CJ-series User Defined CAN Unit Operation Manual for NJ-series CPU Unit (W517)
Function
<Operation specifications>
TRUE:
CAN communications enabled and unit
state is ST5 (communicating).
FALSE:
CAN communications disabled and unit
state is not ST5 (communicating).
Default: FALSE
<Operation specifications>
TRUE:
No new configured CAN message
received since last Unit Cyclic refresh.
FALSE:
New configured CAN message received
since last Unit Cyclic refresh.
Default: FALSE
<Operation specifications>
TRUE:
Send queue overflow occurred. Over-
flowed messages will be delayed. Reset
to FALSE when *_EnblCANComm is
switched from TRUE→FALSE in state
ST5 (communicating).
FALSE:
The send queue has accepted all mes-
sages to be sent.
Default: FALSE
<Operation specifications>
TRUE:
Receive queue overflow occurred. Some
messages have been discarded. Reset to
FALSE when *_EnblCANComm is
switched from FALSE→TRUE in state
ST4 (configured).
FALSE:
All messages received were processed.
Default: FALSE

Advertisement

Table of Contents
loading