4.3 - Short-circuit stability current for all units
Short-circuit stability current for all units using the TN
system (earthing system type): 50 kA (conditional system
short-circuit current Icc/Icf at the unit connection point as
rms value).
4.4 - Compressor electrical data 30XW
Compressor
I Nom (A)*
06TTW266
84
06TTW301
96
06TTW356
113
06TUW483
144
06TUW554
162
06TVW680
193
06TVW753
214
06TVW819
232
06TTA266
95
06TTA301
109
06TTA356
125
06TUA483
162
06TUA554
171
210
06TVA680
06TVA753
230
06TVA819
250
*
Value at standard Eurovent conditions: evaporator entering/leaving water temperature = 12°C/7°C, condenser entering/leaving water temperature = 30°C/35°C.
** Value at maximum capacity and nominal voltage (400 V)
Legend
MHA - Maximum compressor operating current, limited by the unit (current given for maximum capacity at 360 V)
LRYA - Locked rotor current for star connection (connection during compressor start-up)
LRDA - Locked rotor current for delta connection
4.5 - Compressor usage per circuit (A, B)
30XW
254
304
Units without option 150
06TTW266
A
-
06TTW301
-
A
06TTW356
-
-
06TUW483
-
-
06TUW554
-
-
-
-
06TVW680
06TVW753
-
-
06TVW819
-
-
Units with option 150
06TTA266
A
-
06TTA301
-
A
06TTA356
-
-
06TUA483
-
-
06TUA554
-
-
06TVA680
-
-
06TVA753
-
-
06TVA819
-
-
I Max (A)**
I Max (A)**
Option 150B
123
109
145
129
160
142
217
191
242
212
295
278
317
290
351
325
160
125
185
144
200
156
275
215
300
234
400
312
430
335
460
359
354
402
552
652
452
562
712
512
602
-
-
-
-
-
-
-
-
A
-
-
-
-
A
-
-
-
-
A
-
-
-
-
A
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
A
-
-
-
-
A
-
-
-
-
A
-
-
-
-
A
-
-
-
-
-
-
-
-
All units are equipped with protection fuses located in the
control box immediately downstream from the unit connec-