Removing the Leak Prevention Caps

Removing the Leak Prevention Caps
Before brazing the field-supplied refrigerant piping to the outdoor unit connections, the leak prevention caps MUST be removed from the
liquid, high pressure vapor, and low pressure vapor pipe connections.
• Verify that the valve stems in the service ports are closed (see next page).
• Remove the leak prevention caps from the liquid, high pressure vapor, and low pressure vapor pipe outdoor unit connections.
• Use the Schrader valves on the liquid, high pressure vapor, and low pressure vapor pipes to perform the leak / pressure, triple evacuation,
and trim charge procedures.
Location of the Leak Prevention Caps.
Liquid Pipe
Low Pressure
Vapor Pipe
Leak
Prevention Cap
Line connection dimensions in the specification tables and in LATS are field piping dimensions, NOT the dimensions on the outdoor unit connec-
tions themselves. Adapters may be needed to connect the field piping to the correct outdoor unit connection (adapters are factory supplied with the
outdoor unit).