Dip Switch Settings For Use With Gen 4 Indoor Units - LG ARUM072BTE5 Installation Manual

Multi v 5 series
Hide thumbs Also See for ARUM072BTE5:
Table of Contents

Advertisement

Generation 4 Equipment
The latest versions of LG's indoor units are designated Generation 4 (Gen 4). For Gen 4 indoor units to operate with Gen 4 indoor unit fea-
tures, the air conditioning system must meet the following requirements:
• All indoor units, heat recovery units, and air / water source units
must be Gen 4 or higher.
• All air / water source units must have Gen 4 or higher software
installed.
• Air / water source units DIP switch 3 must be set to ON
(factory default setting is OFF).
• All controllers must support Gen 4 indoor unit features.
The figure at right shows the outdoor unit DIP switch. The "System
Component Combinations and Operation Status" table lists how
combining different components will affect system operation. The
"Serial Numbers or Air / Water Source Units with Gen 4 or Higher
Software" table lists the serial numbers of air and water source
units that have Gen 4 or higher software. All air and water source
units, indoor units, heat recovery units, and controllers in a system
must be Gen 4 compatible or the system will not operate with Gen 4
indoor unit features.
Table 43: System Component Combinations and Operation Status.
Air / Water
Indoor Unit(s)**
Source Units*
Gen 4 or Higher
Gen 4 ONLY
Gen 4 or Higher
Gen 4 ONLY
Gen 4 or Higher
Gen 4 ONLY
Any combination of
Gen 4 or Higher
Gen 2 and Gen 4
Any combination of
Gen 4 or Higher
Gen 2 and Gen 4
Any combination of
Gen 2
Gen 2 and Gen 4
*Gen 4 or Higher Air / Water Source Units = Multi V 5, Multi V IV or Multi V Water IV with Gen 4 or Higher software (see table below for Gen
4 or higher serial numbers) or Multi V S.
Gen 2 Air / Water Source Units = Multi V II, Multi V III, Multi V IV without Gen. 4 software, Multi V Water II, Multi V Water IV without Gen. 4
software, Multi V Mini, Multi V Water Mini, or Multi V Space II.
**Gen 4 Indoor Units model numbers end in "4"; Gen 2 Indoor Units model numbers end in "2" or an "A", including Hydro Kit.
***DIP Switch No. 3 on Gen 2 air / water source units is not related to Gen 4 features as it is with Gen 4 air / water source units.
****0A Model Heat Recovery units are not for use with Multi V 5, Multi V IV, Multi V Water IV, or Multi V III heat recovery systems.
Table 44: Serial Numbers of Air / Water Source Units with Gen 4 or Higher Software.
Air / Water Source Unit Model
Type
Serial Number of Air / Water
Source Units with
Gen 4 or Higher Software

DIP Switch Settings for Use with Gen 4 Indoor Units

Heat Recovery Unit(s)
Model 2A ONLY
Model 2A ONLY
Any combination of
Models 1A, 2A
Model 2A ONLY
Any combination of
Models 1A, 2A
Any combination of Models
0A****, 1A, 2A
Multi V Air Source
Multi V Air Source
Heat Pump
502********* and Higher
503********* and Higher
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
PRE-COMMISSIONING
Location and Setting of Outdoor Unit DIP Switch 3.
Air/Water Source Unit DIP Switch No. 3
ON
OFF
1 2
3
4
5
6
1 2
3
4
5
6
Outdoor Unit
DIP Switch
No. 3
Must be ON
System will operate WITH Gen. 4 indoor unit features.
System will operate but WITHOUT Gen. 4 indoor unit
OFF
Must be OFF
(factory default)
Does NOT include Gen. 4 features. System will not
Must be OFF
operate if DIP Switch No. 3 is ON, and an error code
(factory default)
Must be OFF
(factory default)
N/A***
Multi V IV Water Source
Heat Recovery
Heat Pump
ON
OFF
1 2
3
4
7
1 2
3
4
7
Operation Status
features.
will be generated.
Does not include Gen. 4 features.
Multi V IV Water Source
Heat Recovery
504********* and Higher
5
6
7
5
6
7
119

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents