(b) Grounding a twisted pair cable
• Always use shielded twisted pair cables for connection to
10BASE-T and 100BASE-TX connectors.
For the shielded twisted pair cable, strip a part of the jacket
as shown below and ground the exposed shield section to
the ground as much as possible.
(c) Grounding a Ver.1.10-compatible CC-Link dedicated cable
Be sure to ground the cable shield that is connected to the CC-
Link module close to the exit of control panel or to any of the
CC-Link stations within 30cm from the module or stations.
The CC-Link Ver. 1.10 compatible cable is a shielded cable.
Strip a part of the jacket as shown below and ground the
exposed shield section to the ground as much as possible.
Always use the specified CC-Link Ver. 1.10 compatible cable.
Connect the CC-Link module and the CC-Link stations to the
FG line inside the control panel at the FG terminal as shown
below.
Master module
(Blue)
DA
Terminating
(White)
resistor
DB
(Yellow)
DG
SLD
FG
Shielded twisted pair cable
Shield
CC-Link Ver.1.10 compatible cable
Shield
Remote module
(Blue)
DA
(White)
DB
(Yellow)
DG
SLD
CC-Link Ver.1.10
FG
compatible cable
49
(Blue)
(Blue)
(White)
(White)
(Yellow)
(Yellow)
CC-Link Ver.1.10
compatible cable
Local module
DA
Terminating
resistor
DB
DG
SLD
FG