S S t t a a r r t t u u p p
N N o o t t e e : : Sufficient cooling load must be visible to
refrigerant circuit controls for mechanical
refrigeration to operate. If necessary,
temporarily reduce the discharge air setpoint
to verify the refrigeration cycle operation.
9. Check voltage at all compressor terminals to ensure
it is within 10% of nameplate voltage.
10. Check voltage imbalance from these three voltage
readings at each compressor. Maximum allowable
voltage imbalance, phase to phase is 2%.
11. Start the first step compressor only.
12. Check amp draw at compressor terminals. RLA and
LRA are on the unit nameplate.
13. Measure amp draw at evaporator fan motor
terminals. FLA data is on the motor nameplate.
14. As soon as a compressor starts, verify correct
rotation. If a scroll compressor is allowed to run
backwards for even a very short period of time,
internal compressor damage could occur and
compressor life could be reduced. When rotating
backwards scroll compressors make a loud noise,
do not pump, and draw about 1/2 expected amps,
and low side shell gets hot. Immediately shut off a
compressor rotating backwards and correct wiring.
N N O O T T I I C C E E
C C o o m m p p r r e e s s s s o o r r D D a a m m a a g g e e ! !
F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w i i n n s s t t r r u u c c t t i i o o n n s s b b e e l l o o w w c c o o u u l l d d r r e e s s u u l l t t i i n n
c c o o m m p p r r e e s s s s o o r r d d a a m m a a g g e e . .
I I m m p p r r o o p p e e r r p p o o w w e e r r p p h h a a s s i i n n g g w w i i l l l l c c a a u u s s e e c c o o m m p p r r e e s s s s o o r r t t o o
r r u u n n b b a a c c k k w w a a r r d d s s . . C C o o m m p p r r e e s s s s o o r r c c o o u u l l d d b b e e r r u u n n n n i i n n g g
b b a a c c k k w w a a r r d d s s i i f f i i t t i i s s n n o o i i s s y y , , l l o o w w s s i i d d e e s s h h e e l l l l g g e e t t s s h h o o t t , ,
s s u u c c t t i i o o n n p p r r e e s s s s u u r r e e d d o o e e s s n n o o t t d d r r o o p p w w i i t t h h i i n n 5 5 s s e e c c o o n n d d s s
a a f f t t e e r r s s t t a a r r t t u u p p , , a a n n d d c c o o m m p p r r e e s s s s o o r r o o n n l l y y d d r r a a w w s s ½ ½
e e x x p p e e c c t t e e d d a a m m p p s s . . S S t t o o p p t t h h e e c c o o m m p p r r e e s s s s o o r r i i m m m m e e d d i i a a t t e e l l y y
a a n n d d h h a a v v e e a a q q u u a a l l i i f f i i e e d d e e l l e e c c t t r r i i c c i i a a n n o o r r t t e e c c h h n n i i c c i i a a n n
p p r r o o p p e e r r l l y y t t r r a a i i n n e e d d i i n n 3 3 p p h h a a s s e e p p o o w w e e r r c c o o r r r r e e c c t t t t h h e e
w w i i r r i i n n g g . .
15. A A i i r r C C o o o o l l e e d d O O n n l l y y : Check condenser fans for proper
rotation. From top of unit, correct rotation direction
is clockwise. If running backwards, correct wiring.
W W A A R R N N I I N N G G
R R o o t t a a t t i i n n g g C C o o m m p p o o n n e e n n t t s s ! !
F F a a i i l l u u r r e e t t o o d d i i s s c c o o n n n n e e c c t t p p o o w w e e r r b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g c c o o u u l l d d
r r e e s s u u l l t t i i n n r r o o t t a a t t i i n n g g c c o o m m p p o o n n e e n n t t s s c c u u t t t t i i n n g g a a n n d d s s l l a a s s h h i i n n g g
t t e e c c h h n n i i c c i i a a n n w w h h i i c c h h c c o o u u l l d d r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r s s e e r r i i o o u u s s
i i n n j j u u r r y y . .
D D u u r r i i n n g g i i n n s s t t a a l l l l a a t t i i o o n n , , t t e e s s t t i i n n g g , , s s e e r r v v i i c c i i n n g g a a n n d d
t t r r o o u u b b l l e e s s h h o o o o t t i i n n g g o o f f t t h h i i s s p p r r o o d d u u c c t t i i t t m m a a y y b b e e
n n e e c c e e s s s s a a r r y y t t o o w w o o r r k k w w i i t t h h l l i i v v e e a a n n d d e e x x p p o o s s e e d d r r o o t t a a t t i i n n g g
c c o o m m p p o o n n e e n n t t s s . . H H a a v v e e a a q q u u a a l l i i f f i i e e d d o o r r l l i i c c e e n n s s e e d d s s e e r r v v i i c c e e
i i n n d d i i v v i i d d u u a a l l w w h h o o h h a a s s b b e e e e n n p p r r o o p p e e r r l l y y t t r r a a i i n n e e d d i i n n
h h a a n n d d l l i i n n g g e e x x p p o o s s e e d d r r o o t t a a t t i i n n g g c c o o m m p p o o n n e e n n t t s s , , p p e e r r f f o o r r m m
t t h h e e s s e e t t a a s s k k s s . .
82
16. After 10 minutes, start second compressor of
manifold circuits.
17. Allow 10 minutes for circuit operation to stabilize at
full load.
18. Complete charging, if required.

Final Refrigerant Charge

If full charge was not used during installation, follow
these steps:
1. Determine remaining charge required by
subtracting charge added during
Refrigerant Charging," p. 41
2. With all circuit compressors running, SLOWLY
meter remaining R-410A into the suction line from
the LIQUID charging connection.
N N O O T T I I C C E E
C C o o m m p p r r e e s s s s o o r r D D a a m m a a g g e e ! !
O O v v e e r r c c h h a a r r g g i i n n g g s s y y s s t t e e m m c c o o u u l l d d r r e e s s u u l l t t i i n n c c o o m m p p r r e e s s s s o o r r
f f a a i i l l u u r r e e a a n n d d / / o o r r r r e e d d u u c c e e d d c c o o m m p p r r e e s s s s o o r r l l i i f f e e . .
D D o o n n o o t t o o v v e e r r c c h h a a r r g g e e s s y y s s t t e e m m . . E E x x c c e e s s s s i i v v e e r r e e f f r r i i g g e e r r a a n n t t
c c h h a a r r g g i i n n g g c c a a n n c c a a u u s s e e c c o o m m p p r r e e s s s s o o r r l l i i q q u u i i d d s s l l u u g g g g i i n n g g a a t t
s s t t a a r r t t u u p p , , a a n n d d c c o o n n d d i i t t i i o o n n s s w w h h e e r r e e c c o o m m p p r r e e s s s s o o r r s s a a n n d d / / o o r r
c c o o n n d d e e n n s s e e r r f f a a n n s s s s h h o o r r t t c c y y c c l l e e . .
N N O O T T I I C C E E
C C o o m m p p r r e e s s s s o o r r D D a a m m a a g g e e ! !
F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w i i n n s s t t r r u u c c t t i i o o n n s s b b e e l l o o w w c c o o u u l l d d r r e e s s u u l l t t i i n n
c c o o m m p p r r e e s s s s o o r r f f a a i i l l u u r r e e a a n n d d / / o o r r r r e e d d u u c c e e d d c c o o m m p p r r e e s s s s o o r r
l l i i f f e e . .
T T o o p p r r e e v v e e n n t t c c o o m m p p r r e e s s s s o o r r l l i i q q u u i i d d s s l l u u g g g g i i n n g g , , o o n n l l y y a a d d d d
l l i i q q u u i i d d i i n n t t h h e e s s u u c c t t i i o o n n l l i i n n e e w w h h e e n n t t h h e e c c o o m m p p r r e e s s s s o o r r i i s s
r r u u n n n n i i n n g g . . U U s s e e e e x x t t r r e e m m e e c c a a u u t t i i o o n n t t o o m m e e t t e e r r l l i i q q u u i i d d
r r e e f f r r i i g g e e r r a a n n t t i i n n t t o o t t h h e e s s u u c c t t i i o o n n l l i i n n e e s s l l o o w w l l y y . . I I f f l l i i q q u u i i d d i i s s
a a d d d d e e d d t t o o o o r r a a p p i i d d l l y y , , c c o o m m p p r r e e s s s s o o r r o o i i l l d d i i l l u u t t i i o o n n a a n n d d o o i i l l
p p u u m m p p o o u u t t c c o o u u l l d d o o c c c c u u r r . .
3. Use an accurate scale to measure and record
amount of R-410A added.
4. After unit has been operating for approximately 30
minutes at full load, measure and record operating
pressures.
A A i i r r C C o o o o l l e e d d O O n n l l y y : Operating pressure measurement
must be made with all condenser fans running.
5. Repeat for other circuits.
6. Confirm, and adjust charge if needed, by checking
subooling at AHRI 340/360 full load operating
conditions (80/67°F entering evap, ~300CFM/ton, 85/
95°F EWT/LWT for water-cooled and 95°F OA for
air-cooled).
Water-cooled subcooling should be 8-10°F
Air-cooled subcooling should be 14-18°F
"Preliminary
from the total.
SCXF-SVX01Q-EN