Code Fault Description
153
Unit manually locked
160
Fan speed threshold not reached
171
Alarm contact 1 active
172
Alarm contact 2 active
173
Alarm contact 3 active
174
Alarm contact 4 active
217
Sensor error
317
Mains frequency outside permissable range
320
DHW Charging temperature, sensor error
324
Input BX, same sensors
325
Input BX/extension module, same sensors
326
Input BX/mixing group, same sensors
327
Extension module, same function
330
Sensor input BX1 without function
331
Sensor input BX2 without function
332
Sensor input BX3 without function
333
Sensor input BX4 without function
335
Sensor input BX21 without function
336
Sensor input BX22 without function
351
Primary controller/system pump, address error
353
Cascade fl ow sensor B10 missing
384
Extraneous Light
385
Mains under voltage
386
Fan speed tolerance
388
DHW sensor no function
432
Function earth not connected
NA
Operating mode button locked - Cannot operate
in DHW or Heating mode (No fault code displayed)
iHE
FAULT CODES (CONTINUED)
Notes
Reset button stuck in
Required fan speed not reached - Faulty fan unit
Condensate blockage
Alarm 2 activated (not confi gured)
Alarm 3 activated (not confi gured)
Alarm 4 activated (not confi gured)
Ionisation current fault.
Check electrical installaiton
Check connections and / or replace faulty sensor (B36)
BX sensor duplicated - check parameters
BX extension module sensor duplicated - check parameters
Bx Mixing Circuit sensor duplicated - check parameters
Extension Modules duplicated - check parameters
BX1 connected but not defi ned - check parameters
BX2 connected but not defi ned - check parameters
BX3 connected but not defi ned - check parameters
BX4 connected but not defi ned - check parameters
BX21 connected but not defi ned - check parameters
BX22 connected but not defi ned - check parameters
Htg Pump (Q14) not confi gured on PCB1
Check connections and confi guration of sensor (B10)
Ionisation current detected before ignition
Mains voltage below 185v - check installation
Fan outside allowed speed tolerance level - replace fan
Tank temperature sensor not confi gured (B3)
No Ignition earth, X1 / X17 not connected or earth fault
Remote system enable operating. Check Link terminals