Fault Codes (Table 3); Heating - Potterton iHE 100/300 Installation And Servicing Instructions

Indirect high efficiency boiler & water heater
Table of Contents

Advertisement

Code Fault Description
10
Outside sensor, error
20
Boiler temperature 1, sensor error
26
Common fl ow temperature, sensor error
28
Flue gas temperature, sensor error
30
Flow temperature 1, sensor error
32
Flow temperature 2, sensor error
40
Return temperature 1, sensor error
50
DHW temperature 1, sensor error
60
Room temperature 1, sensor error
65
Room temperature 2, sensor error
68
Room temperature 3, sensor error
70
Stoarge tank temperature 1, sensor error
83
LPB collision
84
BSB address collision
98
Extension module 1, error
99
Extension module 2, error
100
2 Clock time masters
110
STB lockout
111
Shutdown limit thermostat
121
Flow temperature heating circuit 1 not reached
122
Flow temperature heating circuit 2 not reached
126
DHW charging temperature not reached
127
DHW legionella temperature not reached
128
Loss of fl ame during operation
130
Flue gas temp too high
133
Safety time exceeded
151
BMU Internal error
152
Parameterization error
iHE
FAULT CODES
Notes
Check connections and / or replace faulty sensor
Check connections and / or replace faulty sensor (B2)
Check connections and / or replace faulty sensor (B10)
Check connections and / or replace faulty sensor (B8)
Check connections and / or replace faulty sensor (B1)
Check connections and / or replace faulty sensor (B12)
Check connections and / or replace faulty sensor (B7)
Check connections and / or replace faulty sensor (B3)
Check connections and / or replace faulty sensor (R1)
Check connections and / or replace faulty sensor (R2)
Check connections and / or replace faulty sensor (R3)
Check connections and / or replace faulty sensor (B4)
Duplicate LPB address - Check all PCBs function 6600
Room unit incorrectly confi gured - see function 40
Module 1 confi guration error - Check parameters
Module 2 confi guration error - Check parameters
Only PCB no 1 is set as time master - see Function 6640
Check connector X18a and all fl ow & return sensors
Heat exchanger temperatures have been exceeded
Htg Circuit 1, time temp parameter not reached
Htg Circuit 2, time temp parameter not reached
Check operation and heat up times for DHW
Check operation of appliance
Ionisation current lost after successful ignition
Heat Engine is overheating. Check causes of high temps
Ignition unsuccessful after 5 attempts
Check polarity is not reversed to the appliance
Incorrect / Confl icting parameters input.
35
(B9)
Table 3.0