Maximum Fl Ue Lengths - Potterton iHE 100/300 Installation And Servicing Instructions

Indirect high efficiency boiler & water heater
Table of Contents

Advertisement

Examples:
Concentric Flue Type C
A fl ue system that uses ten straight lengths, three
90° bends, two 45
bends and a horizontal termi-
o
nal.
10 x 1m straight length
3 x 90° bends
2 x 45
bends
o
1 x Horizontal Terminal
Total
(within 18m limit)
Concentric Flue Type C
A system that rises from the Heater and uses
seven straight lengths, four 45° bends and a verti-
cal terminal.
7 x 1m straight lengths
4 x 45° bends
Vertical Terminal
Total
(within 18m limit)
Concentric Flue
Item
1m length
45° bend
90° bend
Horizontal Terminal
Vertical Terminal
Flue Parts
1.0 m Concentric Length
0.5m Concentric Length
Concentric 90° Bend
Concentric 45° Bend
Flue Condense Trap
Horizontal Terminal kit
Terminal Guard
Vertical Terminal kit
Wall Clamp 200mm
iHE
13
10.0
3.0
1.0
1.0
15.0
33
7.0
2.0
1.6
10.6
F.E.L.
1.0
0.5
1.0
1.0
1.6
Part Number
E212
E214
E215
E216
E220
E240
E630
E670
E219
Open Flue Type B
23
The maximum FEL of fl ue in this confi guration is
25 metres.
The air inlet connection to the appliance must
be fi tted with a Debris Guard. Air is drawn from
the room or compartment in which the heater is
installed and therefore the room or compartment
must be ventilated. See Page 11.
The fl ue duct can discharge either vertically or hori-
zontally by selection of the correct fl ue terminal.
The fl ue pipe can be fi tted with 90 and 45 degree
bends as well as extensions.
Example:
A B
system with air collected from the plant room
23
and the fl ue exiting via twelve straight lengths and
four 45° bends to a roof terminal.
4 x 1 m straight lengths of FLUE.
4 x 45° bends of FLUE
1 x Roof Terminal
Total
(within 30m limit)
Conventional Flue
Item
NB Do not include the Twin Adapter
1m length
45° bend
90° bend
Horizontal Terminal
Vertical Terminal
Flue Parts
Flue Clamp, 130 mm
Angle Roof Plate
Flat Roof Plate
1m x 130mm Flue Length
130mm 90° Elbow
130mm 45° Elbow
Debris Guard
15
12.0
2.0
1.6
15.6
F.E.L.
1.0
0.5
1.0
1.0
1.6
Part Number
TBC
TBC
TBC
TBC
TBC
TBC
TBC