Water Connections; Open Vent - Potterton iHE 100/300 Installation And Servicing Instructions

Indirect high efficiency boiler & water heater
Table of Contents

Advertisement

WATER CONNECTIONS

G
ENERAL
The cold water inlet and hot water outlet connection
nipples are identifi ed on top of the appliance.
Connect the cold water feed and hot water outlet
to these nipples with union adaptors for ease of
servicing. Connect the supplied isolating valve to the
drain connection and pipe to a suitable discharge
point.
(See fi g 1.1 for connection locations)
Do not apply excessive torque to these
nipples when making connections. The
use of an appropriate pipe sealing
compound s recommended
C
W
S
- S
OLD
ATER
UPPLY
The appliance may be connected to an open vent or
sealed system supply. When connected to a sealed
system an unvented water kit must be installed with
a minimum water pressure of one bar. The applianc-
es are factory fi tted with temperature and pressure
relief valves. An unvented system must be fi tted by
an approved installer.
C
W
S
- Q
OLD
ATER
UPPLY
In hard water areas scale formation can occur in all
hot water systems and the higher the volume and
hotter the water used, the greater and more prob-
lematic the scale build-up can be. Water treatment
is usually recommended when the hardness levels
measures greater than 150 ppm. For this reason,
base exchange water treatment is strongly recom-
mended in hard water areas.
O
V
D
(F
PEN
ENTED
ESIGN
IG
The tank must be supplied from a cold water feed
cistern and the hot water supply pipe must be fi tted
with an open vent pipe in accordance with BS 5546
and BS 6644. The Water Supply (Water Fittings)
Regulations must be observed when installing the
system.
The cold water feed cistern must have an actual
capacity greater than the hourly recovery rate of the
heater or heaters to which it is fi tted, the minimum
actual capacity allowed for a feed cistern being 227
litres (50 gallons).
The actual cistern capacity is the capacity to the
normal water level of the cistern. All cisterns should
be manufactured to the relevant Standard.
The distance from the normal water level to the top
iHE
YSTEM
T
UALITY AND
REATMENT
2.3)
of the cistern should comply with that specifi ed by
the Water Authorities.
S
R
(F
ECONDARY
ETURN
IG
A Secondary Return may be fi tted to the 1" nipple
at the top of the appliance. In all cases, for serv-
iceability, the recirculation pipe must be fi tted with
a stop valve immediately before the connection
point.
D
-S
E
TRATIFICATION
By virtue of its design a de-stratifi cation pump is
not required.
iHE OPEN VENT EXAMPLE
9
2.5)
Fig 2.3