Minor Faults/Alarms

This section gives information about the causes and possible solutions when a minor fault or alarm occurs. Use
the information in this table to remove the cause of the minor fault or alarm.
Code
Name
AEr
Station Address Setting
Error
CALL
Serial Comm Transmission
Error
EEP
EEPROM Checksum Error
8
Specifications
Item
Model
Communication Profile
Connector
Communication Speed
Ambient Temperature
Humidity
Storage Temperature
Area of Use
Altitude
YASKAWA ELECTRIC SIEP YEUOCL1 01A CANopen-Lift Communication Option Installation Manual
Causes
Option card node address is outside of
the acceptable setting range.
The communications cable wiring is
incorrect.
There is a short circuit or the
communications cable is not connected.
There was a programming error on the
controller side.
The communications circuitry is
damaged.
The termination resistor setting for
MEMOBUS/Modbus communications
is incorrect.
Communication wiring is faulty, there is
a short circuit, or something is not
connected properly.
EEPROM checksum error.
Programming error occurred on the
controller side.
Communications circuitry is damaged.
Specification
SI-L3
CiA-301 Ver. 4.02
CiA-417 Ver. 2.2.0, Profile Velocity and Profile Position
9 pin D-sub connector
10 kbps to 1 Mbps
-10 °C to +50 °C
up to 95% RH (non-condensing)
-20 °C to +60 °C
Indoor (free of corrosive gas, airborne particles, etc.)
Up to 1000 m
Possible Solutions
For CANopen communication, set F6-35
[CANopen Node ID Selection] correctly.
Correct any wiring errors.
• Repair short circuits and connect cables.
• Replace the defective communications cable.
Examine communications at start-up and correct
programming errors.
• Do a self-diagnostics check.
• If the problem continues, replace the control
board or the drive. For information about
replacing the control board, contact Yaskawa or
your nearest sales representative.
On the last drive in a MEMOBUS/Modbus
network, set DIP switch S2 to the ON position to
enable the termination resistor.
Correct any wiring errors.
• If these errors occur, the object dictionary will be
reset to its default values. After the object
dictionary has been changed and object
dictionary contents are then changed, execute a
Store Parameter command (Index = 1010 (Hex)).
• If the object dictionary has not been changed,
execute a Restore Parameter command (Index =
1011 (Hex)).
Check communications at start-up and correct
programming errors.
• Perform a self-diagnostics check.
• If the problem continues, replace either the
control board or the entire drive. For instructions
on replacing the control board, contact Yaskawa
or your nearest sales representative.
8 Specifications
17