TCS-NET General Purpose Interface
6

Setting

1. Setting Terminator Resistor for the TCC-LINK Communication Line
The TCC-LINK consists of TCB-IFCG1TLE units only. When no multiple air conditioners or custom air conditioners
are connected, set SW6-1 of only one TCB-IFCG1TLE unit to ON and insert a 100-ohm terminator resistor into the
TCC-LINK bus. SW6-2 is not used.
SW6
ON
OFF
1 2
Switch settings are ONLY registered at power ON and when the reset switch has been pressed. When changing
DIP Switch settings, be sure to either power down, or press reset switch SW7 to enable changes to be registered.